| Plan Review Notes For Permit 18120381 |
| Permit Number |
18120381 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-01-02 15:02:43 | 1ST REVIEW FBC-2017 MECHANICAL | | | PERMIT #18120381 | | | 1/2/18 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | | 2017 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | | EDITION 2017 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THE R448 REFRIGERANT HAS NOT BEEN CLASSIFIED IN | | | ACCORDANCE WITH ASHRAE 34, AND IS NOT LISTED IN EITHER | | | THE ASHRAE OR FBC M CLASSIFICATION TABLES. | | | | | | SECTION 1103.1 REFRIGERANT CLASSIFICATION. | | | | | | REFRIGERANTS SHALL BE CLASSIFIED IN ACCORDANCE WITH | | | ASHRAE 34 AS LISTED IN TABLE 1103.1. | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|