| Plan Review Notes For Permit 18120356 |
| Permit Number |
18120356 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-12-21 09:00:54 | BUILDING PLAN REVIEW | | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | | | | JOSEAN A. DUPREY | | | PLANS EXAMINER | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6716 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | 1ST REVIEW | | | RESULTS: DENIED | | | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED | | | BELOW. | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | 1. THE SCOPE OF WORK INDICATES WATER PROOFING REPAIRS | | | AT 13 WINDOWS. THE EXACT LOCATION OF THIS 13 WINDOWS IS | | | NOT CLEAR. PLEASE PROVIDE A PLAN WHERE INDICATES THE | | | EXACT LOCATION FOR THE 13 WINDOWS. FBC 107 | | | | | | 2. THE SUBMITTED SPECS INDICATED THE USE OF STOGUARD | | | RAPIDSEAL AND SEALANT BETWEEN THE WINDOW AND | | | CONCRETE/WOOD BUCK. THIS INDICATES THE WINDOW HAVE TO | | | BE REMOVE TO PERFORM THE REPAIR AS PER PRODUCT | | | SPECIFICATION. PLEASE PROVIDE PRODUCT APPROVAL FOR THIS | | | WINDOWS IN ORDER TO SPECIFY THE TYPE OF SCREEWS AND | | | LOCATION FOR RE-INSTALLATION. EXISTING FBC 702; FBC 102 | | | | | | 3. PLEASE PROVIDE PRODUCT SUBMITTALS APPROVED BY THE | | | PROFESSIONAL RESPONSIBLE FOR THE PRODUCT RECOMENDATION. | | | FBC 107 | | | | | | 4. PLEASE, PROVIDE A THIRD PARTY INSPECTOR FOR THIS | | | JOB. FOR ANY QUESTION CONTACT KEN CONRAD TO | | | 561-805-6666. |
|