| 2018-12-14 10:43:16 | BUILDING PLAN REVIEW | | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | | | | JOSEAN A. DUPREY | | | PLANS EXAMINER | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6716 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | 1ST REVIEW | | | RESULTS: DENIED | | | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED | | | BELOW. | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | 1.THE SHINGLES LOCATION IS NOT CLEAR, PLEASE PROVIDE | | | THE ROOF PLAN WHERE INDICATE THE SHINGLES LOCATION. | | | R905.2.2 | | | | | | 2.PLEASE PROVIDE PRODUCT DATA FOR ALL THE ASSEMBLY. | | | 107.2.1.1 FOR ROOF ASSEMBLIES REQUIRED BY THE CODE, THE | | | CONSTRUCTION DOCUMENTS SHALL ILLUSTRATE, DESCRIBE AND | | | DELINEATE THE TYPE OF ROOFING SYSTEM, MATERIALS, | | | FASTENING REQUIREMENTS, FLASHING REQUIREMENTS AND WIND | | | RESISTANCE RATING THAT ARE REQUIRED TO BE INSTALLED. | | | PRODUCT EVALUATION AND INSTALLATION SHALL INDICATE | | | COMPLIANCE WITH THE WIND | | | CRITERIA REQUIRED FOR THE SPECIFIC SITE OR A STATEMENT | | | BY AN ARCHITECT OR ENGINEER CERTIFYING SUITABILITY FOR | | | THE SPECIFIC SITE MUST BE SUBMITTED WITH THE | | | CONSTRUCTION DOCUMENTS. | | | |
|