| Plan Review Notes For Permit 18120334 |
| Permit Number |
18120334 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2019-02-13 10:42:18 | ****CORRECTIONS**** | | | | | | PETER E VALENTI | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6673 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | FBC B 107.2.1 PLEASE CORRECT FOR CLARIFICATION THE CITY | | | OF WEST PALM BEACH "SCHEDULE FOR OPENING PROTECTIVE | | | DEVICES OR ASSEMBLIESS". | | | | | | 1. THE SCHEDULE COLUMN FOR "SHUTTER MOUNTING CONNECTION | | | TYPE" SHOULD HAVE THE LETTER DESIGNATION FROM THE | | | PRODUCT APPROVAL SUCH AS M AND O OR W. | | | (APPEARS TO BE THAT OPENING NUMBER 15 AND 16 ARE | | | IDENTIFIED INCORRECTLY WITH THE DESIGNATIONS OF A AND | | | H). PLEASE RESUBMIT THE CORRECTED SCHEDULE. | | | | | | 2. IT APPEARS THAT SOME OF THE IDENTIFIED/CIRCLED | | | CONNECTIONS ARE NOT APPLICABLE TO THIS PROJECT. PLEASE | | | RESUBMIT THE PRODUCT APPROVAL WITH ONLY THE APPLICABLE | | | CONNECTIONS CIRCLED. |
|