| 2019-01-16 11:22:11 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. RISER DIAGRAM SHOWS #4 WIRE FROM FPL TRANSFORMER TO |
| | METER CAN. THIS WIRE SIZE IS NOT RATED FOR 100 AMPS. |
| | PROVIDE CORRECTION. NEC 310.15(B)(16) |
| | 2. RISER DIAGRAM SHOWS PANEL A HAVING A 100 AMP MAIN. |
| | PANEL SCHEDULE SHOWS THE PANEL AS MAINLUG ONLY. PROVIDE |
| | CORRECTION. WPB FBC 107.2.1; NEC 230.70 |
| | 3. CONDUIT FROM METER CAN TO PANEL A SHOWS AN EQUIPMENT |
| | GROUNDING CONDUCTOR. THIS CONDUIT SHOULD NOT CONTAIN AN |
| | EGC. PROVIDE CORRECTION. NEC 250.6 |
| | 4. RISER DIAGRAM SHOWS THE SERVICE AS 120/240 VOLT, 3 |
| | PHASE, WHICH WOULD HAVE A HIGH LEG. PANEL SCHEDULE |
| | SHOWS THE SERVICE AS 120/208 VOLT, 3 PHASE. PROVIDE |
| | CLARIFICATION AND/OR CORRECTIONS. WPB FBC 107.2.1; NEC |
| | 215.5 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD |
| | SHEETS. |
| | |