| 2019-06-11 09:06:20 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED |
| | SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS |
| | COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY |
| | HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW |
| | COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS. |
| | |
| | 1. CORRECTED. |
| | 2. CORRECTED. |
| | 3. CORRECTED. |
| | 4. CORRECTED WITH NOTE ON PLAN. |
| | 5. CORRECTED. |
| | 6. CORRECTED. |
| | 7. CORRECTED. |
| | 8. PROVIDE ACCURATE LOAD CALCULATION DEMAND FACTORS ARE |
| | NOT PERMITTED TO BE APPLIED TO FEEDERS LESS THAN 100 |
| | AMPS. ALSO, PROVIDE LOAD CALCULATION FOR MAIN SERVICE |
| | TO HOUSE TO CONFIRM THAT THE METER CAN IS OF SUFIICIENT |
| | SIZE FOR THE ADDITIONAL LOAD. FBC RE E3602.2, E3602.2.1 |
| | (NOT PROVIDED. RISER DIAGRAM SHOWS A CIRCUIT FEEDING |
| | THE POOL, BUT THIS IS NOT INCLUDED IN THE PANEL |
| | SCHEDULE OR THE LOAD CALCULATION. NO LOAD CALCULATION |
| | HAS BEEN PROVIDED FOR MAIN HOUSE.) |
| | 9. OK |
| | |
| | NEW COMMENTS: |
| | |
| | 10. PER NOTE BELOW THE COMMENTS, THE CORRECTED SHEETS |
| | ARE REQUIRED TO BE INSERTED INTO THE PLAN WHEN |
| | RESUBMITTING, AND THE OLD SHEETS SHOULD BE REMOVED. |
| | PROVIDE CORRECTION. WPB FBC 107.2.1 |
| | 11. LOAD CALCULATION STATES THAT A 100 AMP SERVICE WILL |
| | BE PROVIDED TO GUEST HOUSE. RISER DIAGRAM SHOWS # 8 |
| | WIRE FEEDING THIS PANEL. THIS WIRE SIZE IS NOT RATED |
| | FOR 100 AMPS. PROVIDE CORRECTION. NEC 310.15(B)(16); |
| | FBC RE E3705.1 |
| | 12. PANEL SCHEDULE SHOWS CIRCUIT # 8 AS A 15 AMP |
| | CIRCUIT AND 14 GAUGE WIRE FOR THE BATHROOM RECEPTACLE. |
| | A MINIMUM OF ONE 20 AMPERE BRANCH CIRCUIT SHALL BE |
| | PROVIDED TO SUPPLY BATHROOM RECEPTACLE OUTLET(S). |
| | PROVIDE CORRECTION. NEC 210.11(C)(3) , FBC RE E3703.4 |
| | |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD |
| | SHEETS. |
| | |
| | SINCERELY, |
| | |
| | JOHN PEARSON |
| | ELECTRICAL PLANS EXAMINER |
| | 561-805-6746 |
| | [email protected] |
| | |
| | |