| 2018-12-28 14:55:10 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #18120229 |
| | 12/28/18 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET M-1.0: A DUCT SMOKE DETECTOR IS REQUIRED IN |
| | THE SUPPLY SYSTEM OF THE 5-TON AC SYSTEM PER SECTION |
| | 606.2.1 FBC M. PLEASE NOTE THAT AN EXEMPTION CAN BE |
| | APPLIED IF THE MANUFACTURER'S SPECIFICATIONS INDICATE |
| | THE SYSTEM IS NOT CAPABLE OF PRODUCING OVER 2000 CFMS |
| | OF SUPPLY AIR. |
| | |
| | 2) THE $50,100.00 VALUE ON THE PERMIT APPLICATION |
| | APPEARS LOW FOR A 3,376 SF. OFFICE RENOVATION. PLEASE |
| | PROVIDE A COPY OF THE CONTRACT, AND AN ITEMIZED COST |
| | BREAKDOWN THAT INCLUDES LABOR, MATERIALS, EQUIPMENT, |
| | FIXTURES, APPLIANCES, AND DESIGN FEES- SECTION 109.3 |
| | WPB. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |