Plan Review Notes
Plan Review Notes For Permit 18120203
Permit Number 18120203
Review Stop E
Sequence Number 1
Notes
Date Text
2018-12-10 07:15:44ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. INDIVIDUAL LEVELS OF PARKING GARAGE NOT LABELED ON
 PLANS. PROVIDE CORRECTION. FBC 107.2.1
  
 2. PROVIDE EXTERIOR LIGHTING CONTROL ON PLANS FOR
 EXTERIOR MONUMENT SIGNS AT ENTRANCES TO PARKING GARAGE.
 ( A NOTE ON THE PLAN WILL SUFFICE) FBC EC 405.2.4
  
 3. PROVIDE DISCONNECTS (120V) FOR EXTERIOR MONUMENT
 SIGNS AS PER NEC 600.6A1
  
 4. PROVIDE WIRING DIAGRAMS FOR EXTERIOR MONUMENT SIGNS.
 FBC 107.2.1
  
 5. PROVIDE UL OR OTHER NRTL LISTING/CUT SHEETS OF
 EXTERIOR MONUMENT SIGNS FOR PRODUCT APPROVAL. FBC
 107.2.1 NEC, 90.7, 110.2, 110.3B
  
 6. ELECTRICAL PLAN IS REQUIRED TO BE DESIGNED AND
 SIGNED/SEALED BY A DESIGN PROFESSIONAL OR SIGNED BY THE
 ELECTRICAL CONTRACTOR QUALIFIER. PROVIDE CORRECTION. FS
 471.003(2)(H); 471.025; WPB FBC 107.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  