| Notes |
| Date |
Text |
| 2018-12-20 12:00:23 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | | | | 1) THE PROVIDED SITE PLAN DOES NOT INDICATE ANY GATE | | | OPENINGS OR SITE ACCESS POINTS. | | | | | | ACCESS POINTS ARE REQUIRED FOR FIRE APPARATUS AND/OR | | | PERSONNEL IN THE EVENT OF EMERGENCY INCIDENTS. | | | | | | PER NFPA 1, CHAPTER 18 FIRE DEPARTMENT ACCESS AND WATER | | | SUPPLY | | | | | | 18.2.3 FIRE DEPARTMENT ACCESS ROADS. | | | 18.2.3.1 REQUIRED ACCESS. | | | 18.2.3.1.1 APPROVED FIRE DEPARTMENT ACCESS ROADS SHALL | | | BE PROVIDED | | | FOR EVERY FACILITY, BUILDING, OR PORTION OF A BUILDING | | | HEREAFTER | | | CONSTRUCTED OR RELOCATED. | | | 18.2.3.1.2 FIRE DEPARTMENT ACCESS ROADS SHALL CONSIST | | | OF ROADWAYS, FIRE | | | LANES, PARKING LOT LANES, OR A COMBINATION THEREOF. | | | | | | 18.2.3.4.1 DIMENSIONS. | | | 18.2.3.4.1.1 FIRE DEPARTMENT ACCESS ROADS SHALL HAVE AN | | | UNOBSTRUCTED | | | WIDTH OF NOT LESS THAN 20 FT (6.1 M). | | | | | | | | | PLEASE PROVIDE THE LOCATION AND WIDTH OF THE GATE THAT | | | CAN BE USED FOR FIRE DEPARTMENT ACCESS. | | | | | | | | | 2) A KNOX PADLOCK IS RECOMMENDED FOR ANY GATE FOR EASE | | | OF ACCESS AND RESECURING. PROVIDING A KNOX PADLOCK WILL | | | REDUCE OR ELIMINATE THE NEED TO CUT CHAINS OR PADLOCKS. | | | | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|