Plan Review Notes
Plan Review Notes For Permit 18120161
Permit Number 18120161
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2018-12-20 12:00:23THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) THE PROVIDED SITE PLAN DOES NOT INDICATE ANY GATE
 OPENINGS OR SITE ACCESS POINTS.
  
 ACCESS POINTS ARE REQUIRED FOR FIRE APPARATUS AND/OR
 PERSONNEL IN THE EVENT OF EMERGENCY INCIDENTS.
  
 PER NFPA 1, CHAPTER 18 FIRE DEPARTMENT ACCESS AND WATER
 SUPPLY
  
 18.2.3 FIRE DEPARTMENT ACCESS ROADS.
 18.2.3.1 REQUIRED ACCESS.
 18.2.3.1.1 APPROVED FIRE DEPARTMENT ACCESS ROADS SHALL
 BE PROVIDED
 FOR EVERY FACILITY, BUILDING, OR PORTION OF A BUILDING
 HEREAFTER
 CONSTRUCTED OR RELOCATED.
 18.2.3.1.2 FIRE DEPARTMENT ACCESS ROADS SHALL CONSIST
 OF ROADWAYS, FIRE
 LANES, PARKING LOT LANES, OR A COMBINATION THEREOF.
  
 18.2.3.4.1 DIMENSIONS.
 18.2.3.4.1.1 FIRE DEPARTMENT ACCESS ROADS SHALL HAVE AN
 UNOBSTRUCTED
 WIDTH OF NOT LESS THAN 20 FT (6.1 M).
  
  
 PLEASE PROVIDE THE LOCATION AND WIDTH OF THE GATE THAT
 CAN BE USED FOR FIRE DEPARTMENT ACCESS.
  
  
 2) A KNOX PADLOCK IS RECOMMENDED FOR ANY GATE FOR EASE
 OF ACCESS AND RESECURING. PROVIDING A KNOX PADLOCK WILL
 REDUCE OR ELIMINATE THE NEED TO CUT CHAINS OR PADLOCKS.
  
  
  
 PETER LEDUC
 FIRE MARSHAL