| Plan Review Notes For Permit 18120139 |
| Permit Number |
18120139 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-12-07 17:30:36 | NEW ROOFING (MASTER 17041276)BUILDING REVIEW COMMENTS | | | CODE: FBC 5TH EDITION (2014) AND CITY AMENDMENTS. | | | | | | 1- ROOFING CONTRACTOR SUBMITTED RIDGE VENT FLORIDA | | | PRODUCT APPROVAL FL6267-R14. PLANS DON'T SHOW THESE | | | VENTS. ARCHITECT OF RECORD NEEDS TO REVISE PLANS AS | | | REQUIRED. SEC. 1203 FBC. | | | | | | 2- FLAT ROOF: | | | PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS (2 | | | COPIES) AS REQUIRED BY GENERAL LIMITATION #7 ON LAST | | | PAGE OF NOA 15-0622.21 SUBMITTED TO RESIT THE WIND | | | LOADS. SEC. 1609.1 FBC. | | | | | | 3- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING | | | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS | | | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. | | | | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE/VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | PLEASE DON'T STAPLE OLD DRAWINGS. SUBMIT OLD DRAWINGS | | | FOR REFERENCE. | | | | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] |
|