| Date |
Text |
| 2018-12-19 17:34:59 | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | NOT ENOUGH ELECTRICAL DETAIL TO REVIEW. | | | | | | NEED TO SHOW DISCONNECTS PER 600.6(A)(1) | | | | | | CONTROLS PER FBC EC 405.2.4 | | | | | | EXTERIOR LIGHTING CONTROLS. LIGHTING NOT DESIGNATED FOR | | | DUSK-TO-DAWN OPERATION SHALL BE CONTROLLED BY EITHER A | | | COMBINATION OF A PHOTOSENSOR AND A TIME SWITCH, OR AN | | | ASTRONOMICAL TIME SWITCH. LIGHTING DESIGNATED FOR | | | DUSK-TO-DAWN OPERATION SHALL BE CONTROLLED BY AN | | | ASTRONOMICAL TIME SWITCH OR PHOTOSENSOR. ALL TIME | | | SWITCHES SHALL | | | BE CAPABLE OF RETAINING PROGRAMMING AND THE TIME | | | SETTING DURING LOSS OF POWER FOR A PERIOD OF AT LEAST | | | 10 HOURS. FBC CE 405.2.4 |
|