| 2019-01-15 13:54:27 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH |
| | EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| | FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | 1ST REVIEW: |
| | PLUMBING COMMENTS: DENIED |
| | |
| | 1. RE: PLAN SHEET A3.1.1; BREAK ROOM CABINETRY AT ROOMS |
| | 840.2, 850.2, 800.3 AND 810.5 DOES NOT PROVIDE FOR |
| | PARALLEL CLEAR FLOOR SPACE AS REQUIRED BY FBC ACC 305. |
| | THE SINK MUST BE SET A MINIMUM OF 24" CENTER TO THE |
| | CLOSEST OBSTRUCTION. SIDE ELEVATION OF SINK DETAIL DOES |
| | NOT ALLOW FOR A FORWARD APPROACH.PLEASE PROVIDE CLEAR |
| | FLOOR SPACE FOR EACH BREAKROOM SINK AS REQUIRED BY FBC |
| | ACC SECTION 602 PER WPB FBC 107.2.1. |
| | 2. RE: PLAN SHEET P2.1; KEY NOTE #6. SANITARY RUN BELOW |
| | SLAB AS NOTED ON P5.1 IS 2" IN SIZE AND SHALL BE RUN |
| | WITH A 2% SLOPE TO MEET THE REQUIREMENTS OF FBC PL |
| | 704.1. PLEASE CORRECT NOTE 6 TO REFLECT THE REQUIREMENT |
| | PER WPB FBC 107.2.1. |
| | 3. IN ACCORDANCE WITH FBC PL SECTION 712, SUMP AND |
| | SEWAGE EJECTOR PIPING SHALL BE PRESSURE RATED. PER WPB |
| | FBC 107.2.1, PLEASE PROVIDE A SPECIFICATION FOR THE |
| | EJECTOR DISCHARGE PIPING SHOWING COMPLIANCE WITH FBC |
| | 712.3.3, 712.3.3.1 AND 712.3.3.2. |
| | 4. RE: PLAN SHEET P0.1; A SHUT OFF VALVE ON HOT WATER |
| | SUPPLY TO SINK IS REQUIRED PER FBC PL 606.2. CORRECT |
| | IWH CONNECTION DETAIL TO REFLECT THE REQUIREMENT PER |
| | WPB FBC 107.2.1. |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | EMAIL [email protected] |
| | PHONE 561-805-6715 |