| Plan Review Notes For Permit 18120060 |
| Permit Number |
18120060 |
|
| Review Stop |
G |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2019-01-10 05:29:49 | 1) I AM CHALLENGING THE VALUATION OF THIS PERMIT. | | | SUBMIT A COPY OF THE BONA FIDE CONTRACT/ WORK ORDER FOR | | | THIS JOB. VALUATION SHALL INCLUDE THE COST OF OWNER | | | SUPPLIED ITEMS. WPB AMEND. TO FBC SEC. 109.3. | | | 2) SHOW THE BTU LOAD OF THE WATER HEATER ON THE PLANS. | | | 3) A UNION IS REQUIRED WITHIN ONE FOOT UPSTREAM OR | | | DOWNSTREAM OF THE REGULATOR. 2017 FBC- FUEL GAS SEC. | | | 4.10.2. | | | 4) A SHUTOFF VALVE IS REQUIRED IMMEDIATELY AHEAD OF THE | | | MP REGULATOR. 2017 FBC-FUEL GAS SEC.409.4. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | | | | | | | |
|