Plan Review Notes
Plan Review Notes For Permit 18120060
Permit Number 18120060
Review Stop G
Sequence Number 1
Notes
Date Text
2018-12-18 10:37:271) I AM CHALLENGING THE VALUATION OF THIS PERMIT.
 SUBMIT A COPY OF THE BONA FIDE CONTRACT/ WORK ORDER FOR
 THIS JOB. VALUATION SHALL INCLUDE THE COST OF OWNER
 SUPPLIED ITEMS. WPB AMEND. TO FBC SEC. 109.3.
 2) SUBMIT TWO COPIES OF THE MANUFACTURER'S
 SPECIFICATIONS FOR THE TANKLESS WATER HEATER AND THE
 COOKTOP. THE APPLIANCES SHALL BE LISTED AND LABELED PER
 2017 FBC-FUEL GAS SEC. 301.3. WPB AMEND. TO FBC SEC.
 107.1.
 3) SUBMIT TWO COPIES OF A FLOOR PLAN THAT CLEARLY SHOWS
 THE LOCATION OF THE WATER HEATER. IS IT BEING INSTALLED
 INSIDE OR OUTSIDE? IF INSTALLED OUTDOORS IT SHALL BE A
 MINIMUM OF 4 FEET FROM ANY BUILDING OPENINGS PER THE
 MANUF. INSTALLATION INSTRUCTIONS. IF INSTALLED INSIDE,
 PROVIDE DETAILS ON THE VENT, VENT LOCATION, HEIGHT
 ABOVE ROOF, ETC. INSTALLATION SHALL COMPLY WITH
 MANUFACTURER'S INSTALLATION MANUAL.
 4) SUBMIT TWO COPIES OF THE INSTALLATION INSTRUCTIONS
 FOR THE PRESSURE REGULATOR. WPB AMEND. TO FBC SEC.
 107.1.
 5) SHOW THE BTU LOAD OF THE WATER HEATER ON THE PLANS.
 6) A UNION IS REQUIRED WITHIN ONE FOOT UPSTREAM OR
 DOWNSTREAM OF THE REGULATOR. 2017 FBC- FUEL GAS SEC.
 4.10.2.
 7) A SHUTOFF VALVE IS REQUIRED IMMEDIATELY AHEAD OF THE
 MP REGULATOR. 2017 FBC-FUEL GAS SEC.409.4.
 8) THE DISTANCE OF 5 FEET FROM THE METER TO THE
 FURTHEST OUTLET SHALL BE VERIFIED. THIS DISTANCE DOES
 NOT SEEM CORRECT.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved