| Date |
Text |
| 2018-12-07 14:45:10 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | |
| | 1) SHEET A 1.2 - THERE IS NO INDICATIONS OF THE COMMON |
| | PATH OF TRAVEL DISTANCE WITHIN THE NEW TENANT SPACE TO |
| | THE 1 EXIT. |
| | |
| | PLEASE REVIEW AND PROVIDE. |
| | |
| | |
| | |
| | 2) SHEET A 1.2 - THERE IS AN INDICATION OF A S 2 |
| | OCCUPANCY. DOES THIS INDICATE THE EXISTING OCCUPANCY OR |
| | THE PROPOSED OCCUPANCY OF THE NEWLY CREATED TENANT |
| | SPACE? |
| | |
| | PLEASE PROVIDE THE PROPOSED OCCUPANCY OF THE NEW TENANT |
| | SPACE AND ENSURE THE 1 EXIT MEETS THE REQUIREMENTS OF |
| | THAT SPACE PER THE FLORIDA FIRE PREVENTION CODE. |
| | |
| | |
| | |
| | |
| | |
| | 3) SHEET A 1.2 - ONLY ONE EXIT IS INDICATED FOR THE NEW |
| | TENANT SPACE. IF THE ANSWER TO # 2 IS NEW BUSINESS: |
| | |
| | PER NFPA 101, CHAPTER 38, NEW BUSINSESS OCCUPACNY |
| | |
| | |
| | 38.2.4 NUMBER OF MEANS OF EGRESS. |
| | 38.2.4.1 MEANS OF EGRESS SHALL COMPLY WITH ALL OF THE |
| | FOLLOWING, EXCEPT |
| | AS OTHERWISE PERMITTED BY 38.2.4.2 THROUGH 38.2.4.6: |
| | (1) THE NUMBER OF MEANS OF EGRESS SHALL BE IN |
| | ACCORDANCE WITH |
| | SECTION 7.4. |
| | (2) NOT LESS THAN TWO SEPARATE EXITS SHALL BE PROVIDED |
| | ON EVERY STORY. |
| | (3) NOT LESS THAN TWO SEPARATE EXITS SHALL BE |
| | ACCESSIBLE FROM EVERY |
| | PART OF EVERY STORY. |
| | |
| | 38.2.4.2 EXIT ACCESS, AS REQUIRED BY 38.2.4.1(3), SHALL |
| | BE PERMITTED TO |
| | INCLUDE A SINGLE EXIT ACCESS PATH FOR THE DISTANCES |
| | PERMITTED AS COMMON |
| | PATHS OF TRAVEL BY 38.2.5.3. |
| | |
| | 38.2.4.3 A SINGLE EXIT SHALL BE PERMITTED FOR A ROOM OR |
| | AREA WITH A TOTAL |
| | OCCUPANT LOAD OF LESS THAN 100 PERSONS, PROVIDED THAT |
| | ALL OF THE |
| | FOLLOWING CRITERIA ARE MET: |
| | (1) THE EXIT SHALL DISCHARGE DIRECTLY TO THE OUTSIDE AT |
| | THE LEVEL OF EXIT |
| | DISCHARGE FOR THE BUILDING. |
| | (2) THE TOTAL DISTANCE OF TRAVEL FROM ANY POINT, |
| | INCLUDING TRAVEL WITHIN |
| | THE EXIT, SHALL NOT EXCEED 100 FT (30 M). |
| | (3) THE TOTAL DISTANCE OF TRAVEL SPECIFIED IN |
| | 38.2.4.3(2) SHALL BE ON THE |
| | SAME STORY, OR, IF TRAVERSING OF STAIRS IS NECESSARY, |
| | SUCH STAIRS SHALL |
| | NOT EXCEED 15 FT (4570 MM) IN HEIGHT, AND BOTH OF THE |
| | FOLLOWING |
| | ALSO SHALL APPLY: |
| | (A) INTERIOR STAIRS SHALL BE PROVIDED WITH COMPLETE |
| | ENCLOSURES TO |
| | SEPARATE THEM FROM ANY OTHER PART OF THE BUILDING, WITH |
| | NO |
| | DOOR OPENINGS THEREIN. |
| | (B) A SINGLE OUTSIDE STAIR IN ACCORDANCE WITH 7.2.2 |
| | SHALL BE |
| | PERMITTED TO SERVE ALL STORIES PERMITTED WITHIN THE 15 |
| | FT (4570 |
| | MM) VERTICAL TRAVEL LIMITATION. |
| | |
| | 38.2.4.6 A SINGLE MEANS OF EGRESS SHALL BE PERMITTED |
| | FOR A |
| | MAXIMUM TWO-STORY, SINGLE-TENANT SPACE OR BUILDING |
| | PROVIDED |
| | THAT BOTH OF THE FOLLOWING CRITERIA ARE MET: |
| | (1) THE BUILDING IS PROTECTED THROUGHOUT BY AN |
| | APPROVED, SUPERVISED |
| | AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH |
| | 9.7.1.1(1). |
| | (2) THE TOTAL TRAVEL TO THE OUTSIDE DOES NOT EXCEED 100 |
| | FT (30 M). |
| | |
| | |
| | PLEASE REVIEW AND PROVIDE DETAILS FOR COMPLIANCE. |
| | |
| | |
| | |
| | |
| | 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | |
| | 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |