2019-01-23 09:59:572017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 18120049
 ADD: 1045 CHARLOTTE AVE.
 CONT: POWERSECURE
 TEL: 321-422-2713
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. JAN. 23/2019
 ACTION: DENIED
  
 1) ONLY A SINGLE ELECTRICAL SHEET WAS SUBMITTED. THE E1
 SHEET NOTE 4 INDICATED THIS IS A REPLACEMENT GENERATOR
 ON THE EXTERIOR OF THE BUILDING. THE GENERATOR WILL BE
 HOUSED IN A WEATHERPROOF ENCLOSURE.
 THE PLAN IS NOT CLEAR IF THE WEATHERTIGHT ENCLOSURE IS
 NEW OR EXISTING. 107.2.1.2 ADDITIONAL INFORMATION IS
 REQUIRED.
  
 2A) FOR THE GENERATOR AND WEATHER TIGHT ENCLOSURE THERE
 WAS NO WIND DESIGN PROVIDED TO KNOW WHAT LOADS ARE TO
 BE RESISTED FOR SLIPPAGE AND MOMENT OF OVERTURNING.
 2017 FBC-B 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
  
 2.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR AND NOMINAL DESIGN WIND SPEED, VASD, AS
 DETERMINED IN ACCORDANCE WITH SECTION 1609.3.1.
  
 2.2. RISK CATEGORY
  
 2.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2.
 HEIGHT AND EXPOSURE. ASCE 7-10 TABLE 30.3.1.
  
 2.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
  
 2.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENTS AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF.
  
 TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING.
  
 1609.3.1 WIND SPEED CONVERSION VULT TO VASD.
  
 2B) IN THIS PERMIT PACKAGE THERE WAS NO INFORMATION
 SUBMITTED FOR ANCHORING OF EITHER THE GENERATOR OR THE
 WEATHER TIGHT ENCLOSURE AND TO WHAT WIND SPEED AND RISK
 FACTOR THE UNIT AND OR HOUSING IS TO BE ANCHORED TOO?
 2017 FBC-B TABLE 1604.5 & 1609.3 FIGURES 1609.3(1) OR
 FIGURE 1609.3(2). 1609.3.1 WIND SPEED CONVERSION VULT
 TO VASD.
  
 3) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  