Plan Review Notes
Plan Review Notes For Permit 18120027
Permit Number 18120027
Review Stop M
Sequence Number 2
Notes
Date Text
2019-02-28 11:54:022ND REVIEW FBC-2017 MECHANICAL
 PERMIT #18120027
 12/17/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) COMMENT #1 FROM THE 1ST REVIEW PRINTED BELOW STILL
 EXISTS. THE 3M FIRE BARRIER DUCT WRAP IS A
 FIRE-RESISTANT WRAP THAT IS USED TO FIRE RATE
 COMMERCIAL KITCHEN GREASE DUCTS, AND IS A LISTED AND
 LABELED AS A FIELD APPLIED GREASE DUCT ENCLOSURE
 MATERIAL IN ACCORDANCE WITH THE ASTM E2336 STANDARD-
 SEE SUBMITTED PRODUCT SPECS AND SECTION 506.3.11.2 FBC
 M WHICH STATES "THE SURFACE OF THE DUCT SHALL BE
 CONTINUOUSLY COVERED ON ALL SIDES FROM THE POINT AT
 WHICH THE DUCT ORIGINATES TO THE OUTLET TERMINAL", AND
 "PARTIAL APPLICATION OF A FIELD-APPLIED GREASE DUCT
 ENCLOSURE SHALL NOT BE INSTALLED FOR THE SOLE PURPOSE
 OF REDUCING CLEARANCES TO COMBUSTIBLES AT ISOLATED
 SECTIONS OF GREASE DUCT".
 1) REFER TO SECTION FBC M SECTION 506.5.1.2 IN-LINE FAN
 LOCATION. REVISE THE PLAN AND DETAILS TO SHOW
 COMPLIANCE. WHERE ENCLOSED DUCT SYSTEMS ARE CONNECTED
 TO IN-LINE FANS NOT LOCATED OUTDOORS, THE FAN SHALL BE
 LOCATED IN A ROOM OR SPACE HAVING THE SAME
 FIRE-RESISTANCE RATING AS THE DUCT ENCLOSURE. ACCESS
 SHALL BE PROVIDED FOR SERVICING AND CLEANING OF FAN
 COMPONENTS. SUCH ROOMS OR SPACES SHALL BE VENTILATED IN
 ACCORDANCE WITH THE FAN MANUFACTURER'S INSTALLATION
 INSTRUCTIONS.
  
 2) COMMENT #2 PRINTED BELOW STILL EXISTS. PLEASE
 CONSULT WITH THE CAPTIVEAIRE ENGINEER AND ENGINEER OF
 RECORD TO PROVIDE EITHER TEMPERED MAKEUP AIR, OR
 CALCULATIONS TO PROVE THE ADDED COOLING LOADS OF THE
 MAKEUP AIR DO NOT EXCEED THE CAPACITY OF THE HVAC
 SYSTEM. FOR CLARIFICATION THE MAKEUP AIR FOR THE HOOD
 IS BEING PROVIDED BY KSF-1 NOT THE DOAS WHICH IS
 PROVIDING OUTSIDE AIR FOR OCCUPANTS
 2) REFER TO SECTION 508.1.1 MAKEUP AIR TEMPERATURE.
 REVISE THE PLAN AND DETAILS TO SHOW COMPLIANCE.
 THE TEMPERATURE DIFFERENTIAL BETWEEN MAKEUP AIR AND THE
 AIR IN THE CONDITIONED SPACE SHALL NOT EXCEED 10
 DEGREES F (6 DEGREES C) EXCEPT WHERE THE ADDED HEATING
 AND COOLING LOADS OF THE MAKEUP AIR DO NOT EXCEED THE
 CAPACITY OF THE HVAC SYSTEM.
  
 3) COMMENT #3 STILL EXISTS. M-101 SHOWS TWO MAKEUP AIR
 SUPPLY DROPS INTO THE HOOD- H-1 SHOWS 4 DROPS.
 3) SHEETS H-1 & M-101: THE EXHAUST DUCT CONFIGURATIONS
 AND DUCT SIZES ON THE TWO PLANS DO NOT MATCH. THE KEF
 IS MISLABELED KSF ON H-1.
  
 4) COMMENT #4 STILL EXISTS. THE H-1 PLAN SHOWS A
 MINIMUM 1/8" SLOPE FOR THE GREASE DUCT. SECTION 506.3.7
 REQUIRES A MINIMUM SLOPE OF 1/4" PER FT.
 4) H-1: PROVIDE THE SLOPE OF THE DUCT RUN- SECTION
 506.3.7 FBC M, AND A DETAIL FOR THE GREASE RESERVOIR
 (NOTED AS A GREASE TRAP ON PLAN)- SECTION 506.3.7.1.
  
 6) COMMENT #6 STILL EXISTS. THE NEW SUBMITTAL FOR THE
 GREENHECK INLINE EXHAUST FAN INDICATES THE FAN IS UL
 705 LISTED, NOT UL 762, AND NO SPECIFICATIONS PROVIDED
 FOR THE HOUSING MATERIAL.
 6) H-1: THE GREENHECK EXHAUST FAN SHALL EITHER BE UL
 762 LISTED AND LABELED, OR THE FAN HOUSING SHALL BE
 CONSTRUCTED WITH THE SAME MATERIALS AS REQUIRED FOR
 GREASE DUCTS- SEE SECTIONS 506.5.1 & 506.3.1.1.
  
 9) COMMENT #9 NOT COMPLETELY ADDRESSED. WHAT ARE THE
 DIMENSIONS OF THE GREASE EXHAUST OUTLET? THE REVISED
 H-1 SHOWS DIMENSIONS THAT ARE NOT COMPLETELY LEGIBLE,
 AND THE M-101 PLAN INDICATES 48X30". THE M-101 PLAN
 DOES NOT LIST REQUIRED CLEARANCES.
 9) H-1: PLEASE VERIFY THE EXHAUST OUTLET IS MEETING ALL
 CLEARANCE REQUIREMENTS AS OUTLINED IN SECTION
 506.3.13.3- NOT LESS THAN 10' HORIZONTALLY FROM PARTS
 OF THE SAME OR CONTIGUOUS BUILDINGS, ADJACENT PROPERTY
 LINES, AND NOT LESS THAN 10' ABOVE THE ADJOINING GRADE
 LEVEL,
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER