2018-12-17 13:19:531ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18120027
 12/17/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
  
 1) REFER TO SECTION FBC M SECTION 506.5.1.2 IN-LINE FAN
 LOCATION. REVISE THE PLAN AND DETAILS TO SHOW
 COMPLIANCE.
  
 WHERE ENCLOSED DUCT SYSTEMS ARE CONNECTED TO IN-LINE
 FANS NOT LOCATED OUTDOORS, THE FAN SHALL BE LOCATED IN
 A ROOM OR SPACE HAVING THE SAME FIRE-RESISTANCE RATING
 AS THE DUCT ENCLOSURE. ACCESS SHALL BE PROVIDED FOR
 SERVICING AND CLEANING OF FAN COMPONENTS. SUCH ROOMS OR
 SPACES SHALL BE VENTILATED IN ACCORDANCE WITH THE FAN
 MANUFACTURER'S INSTALLATION INSTRUCTIONS.
  
 2) REFER TO SECTION 508.1.1 MAKEUP AIR TEMPERATURE.
 REVISE THE PLAN AND DETAILS TO SHOW COMPLIANCE.
  
 THE TEMPERATURE DIFFERENTIAL BETWEEN MAKEUP AIR AND THE
 AIR IN THE CONDITIONED SPACE SHALL NOT EXCEED 10
 DEGREES F (6 DEGREES C) EXCEPT WHERE THE ADDED HEATING
 AND COOLING LOADS OF THE MAKEUP AIR DO NOT EXCEED THE
 CAPACITY OF THE HVAC SYSTEM.
  
 3) SHEETS H-1 & M-101: THE EXHAUST DUCT CONFIGURATIONS
 AND DUCT SIZES ON THE TWO PLANS DO NOT MATCH. THE KEF
 IS MISLABLED KSF ON H-1.
  
 4) H-1: PROVIDE THE SLOPE OF THE DUCT RUN- SECTION
 506.3.7 FBC M, AND A DETAIL FOR THE GREASE RESERVOIR
 (NOTED AS A GREASE TRAP ON PLAN)- SECTION 506.3.7.1.
  
 5) H-1: REVISE THE NOTE THAT INDICATES THE CAPTIVE AIRE
 HOOD DRAWINGS ARE SUBMITTED UNDER A SEPARATE PERMIT.
 THOSE DRAWINGS ARE SUBMITTED UNDER THIS PERMIT.
  
 6) H-1: THE GREENHECK EXHAUST FAN SHALL EITHER BE UL
 762 LISTED AND LABELED, OR THE FAN HOUSING SHALL BE
 CONSTRUCTED WITH THE SAME MATERIALS AS REQUIRED FOR
 GREASE DUCTS- SEE SECTIONS 506.5.1 & 506.3.1.1.
  
 7) H-1: REVISE NOTE #6 IN THE FAN SCHEDULE IN
 ACCORDANCE WITH SECTIONS 507.1.1 AND 508.1 FBC M.
 AUTOMATIC OPERATION OF THE FANS IS REQUIRED. PLEASE
 REVIEW THE CODE SECTIONS AND PROVIDE A SEQUENCE OF
 OPERATION IN COMPLIANCE.
  
 8) H-1 & CAPTIVEAIRE SHEET 1: THE EXHAUST AND MAKEUP
 AIR RATES IN THE H-1 FAN SCHEDULE DO MATCH THE REQUIRE
 EXHAUST RATES SHOWN ON THE CAPTIVEAIRE SCHEDULE.
  
 9) H-1: PLEASE VERIFY THE EXHAUST OUTLET IS MEETING ALL
 CLEARANCE REQUIRMENTS AS OUTLINED IN SECTION
 506.3.13.3- NOT LESS THAN 10' HORIZONTALLY FROM PARTS
 OF THE SAME OR CONTIGUOUS BUILDINGS, ADJACENT PROPERTY
 LINES, AND NOT LESS THAN 10' ABOVE THE ADJOINING GRADE
 LEVEL,
  
 10) PLEASE REMOVE THE SMOKE CONTROL FANS FROM THE FAN
 SUBMITTAL PACKAGE, AND RESUBMIT THEM UNDER A SEPARATE
 APPLICATION WITH ALL LABOR, MATERIAL, AND EQUIPMENT
 COSTS ACCOUNTED FOR- SECTION 107.2.1 AND 109.3 WPB.
  
 11) THERE ARE THREE ENGINEERS SUBMITTING PLANS ON THIS
 EXHAUST HOOD SYSTEM. ONE OF THE ENGINEERS MUST BE THE
 EOR AND PROVIDE HIS/HER SHOP DRAWING STAMPS ON THE
 OTHER PLANS- SECTION 107.2.1 WPB.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  