| Date |
Text |
| 2018-12-17 13:19:53 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #18120027 |
| | 12/17/18 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | |
| | 1) REFER TO SECTION FBC M SECTION 506.5.1.2 IN-LINE FAN |
| | LOCATION. REVISE THE PLAN AND DETAILS TO SHOW |
| | COMPLIANCE. |
| | |
| | WHERE ENCLOSED DUCT SYSTEMS ARE CONNECTED TO IN-LINE |
| | FANS NOT LOCATED OUTDOORS, THE FAN SHALL BE LOCATED IN |
| | A ROOM OR SPACE HAVING THE SAME FIRE-RESISTANCE RATING |
| | AS THE DUCT ENCLOSURE. ACCESS SHALL BE PROVIDED FOR |
| | SERVICING AND CLEANING OF FAN COMPONENTS. SUCH ROOMS OR |
| | SPACES SHALL BE VENTILATED IN ACCORDANCE WITH THE FAN |
| | MANUFACTURER'S INSTALLATION INSTRUCTIONS. |
| | |
| | 2) REFER TO SECTION 508.1.1 MAKEUP AIR TEMPERATURE. |
| | REVISE THE PLAN AND DETAILS TO SHOW COMPLIANCE. |
| | |
| | THE TEMPERATURE DIFFERENTIAL BETWEEN MAKEUP AIR AND THE |
| | AIR IN THE CONDITIONED SPACE SHALL NOT EXCEED 10 |
| | DEGREES F (6 DEGREES C) EXCEPT WHERE THE ADDED HEATING |
| | AND COOLING LOADS OF THE MAKEUP AIR DO NOT EXCEED THE |
| | CAPACITY OF THE HVAC SYSTEM. |
| | |
| | 3) SHEETS H-1 & M-101: THE EXHAUST DUCT CONFIGURATIONS |
| | AND DUCT SIZES ON THE TWO PLANS DO NOT MATCH. THE KEF |
| | IS MISLABLED KSF ON H-1. |
| | |
| | 4) H-1: PROVIDE THE SLOPE OF THE DUCT RUN- SECTION |
| | 506.3.7 FBC M, AND A DETAIL FOR THE GREASE RESERVOIR |
| | (NOTED AS A GREASE TRAP ON PLAN)- SECTION 506.3.7.1. |
| | |
| | 5) H-1: REVISE THE NOTE THAT INDICATES THE CAPTIVE AIRE |
| | HOOD DRAWINGS ARE SUBMITTED UNDER A SEPARATE PERMIT. |
| | THOSE DRAWINGS ARE SUBMITTED UNDER THIS PERMIT. |
| | |
| | 6) H-1: THE GREENHECK EXHAUST FAN SHALL EITHER BE UL |
| | 762 LISTED AND LABELED, OR THE FAN HOUSING SHALL BE |
| | CONSTRUCTED WITH THE SAME MATERIALS AS REQUIRED FOR |
| | GREASE DUCTS- SEE SECTIONS 506.5.1 & 506.3.1.1. |
| | |
| | 7) H-1: REVISE NOTE #6 IN THE FAN SCHEDULE IN |
| | ACCORDANCE WITH SECTIONS 507.1.1 AND 508.1 FBC M. |
| | AUTOMATIC OPERATION OF THE FANS IS REQUIRED. PLEASE |
| | REVIEW THE CODE SECTIONS AND PROVIDE A SEQUENCE OF |
| | OPERATION IN COMPLIANCE. |
| | |
| | 8) H-1 & CAPTIVEAIRE SHEET 1: THE EXHAUST AND MAKEUP |
| | AIR RATES IN THE H-1 FAN SCHEDULE DO MATCH THE REQUIRE |
| | EXHAUST RATES SHOWN ON THE CAPTIVEAIRE SCHEDULE. |
| | |
| | 9) H-1: PLEASE VERIFY THE EXHAUST OUTLET IS MEETING ALL |
| | CLEARANCE REQUIRMENTS AS OUTLINED IN SECTION |
| | 506.3.13.3- NOT LESS THAN 10' HORIZONTALLY FROM PARTS |
| | OF THE SAME OR CONTIGUOUS BUILDINGS, ADJACENT PROPERTY |
| | LINES, AND NOT LESS THAN 10' ABOVE THE ADJOINING GRADE |
| | LEVEL, |
| | |
| | 10) PLEASE REMOVE THE SMOKE CONTROL FANS FROM THE FAN |
| | SUBMITTAL PACKAGE, AND RESUBMIT THEM UNDER A SEPARATE |
| | APPLICATION WITH ALL LABOR, MATERIAL, AND EQUIPMENT |
| | COSTS ACCOUNTED FOR- SECTION 107.2.1 AND 109.3 WPB. |
| | |
| | 11) THERE ARE THREE ENGINEERS SUBMITTING PLANS ON THIS |
| | EXHAUST HOOD SYSTEM. ONE OF THE ENGINEERS MUST BE THE |
| | EOR AND PROVIDE HIS/HER SHOP DRAWING STAMPS ON THE |
| | OTHER PLANS- SECTION 107.2.1 WPB. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |