| 2019-04-09 07:49:27 | MECANICAL PLAN REVIEW |
| | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | BUILDING PLANS EXAMINER, PX3169 |
| | 1&2 FAMILY PLANS EXAMINER, SFP306 |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | 2ND REVIEW |
| | RESULTS: DENIED |
| | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED |
| | BELOW. |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | 1.THE PALM BEACH COUNTY PROPERTY APPRAISERS OFFICE LIST |
| | THIS BLDG. AS A 2 STORY MULTI-FAMILY RESIDENTIAL |
| | STRUCTURE WITH 2 UNITS. BUILDING DATA INFO. ON PLAN |
| | PAGE A-1 STATES THIS STRUCTURE IS A 2 STORY STRUCTURE |
| | WITH ONLY 1 UNIT. NO RECORDS ARE AVAILABLE THAT |
| | INDICATES THESE 2 UNITS HAVE BEEN COMBINED. PLEASE |
| | CLARIFY. IDENTIFY UNIT THIS PROPOSED SCOPE OF WORK IS |
| | FOR. IF BOTH UNITS ARE TO RECIEVE WORK, PROVIDE PLAN |
| | AND SCOPE OF WORK FOR 2ND UNIT. |
| | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 2. MECHANICAL SCOPE OF WORK INCLUDES EXHAUST FANS, |
| | MINI-SPLIT AND DRYER EXHAUST. EXHAUST FANS MISSING FROM |
| | PLAN. NO DRYER SHOWN ON PLAN. |
| | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 3. PROVIDE ENERGY CALCULATIONS (MANUAL J), INCLUDE |
| | EQUIPMENT SIZING PER ACCA MANUAL S. M1401.3 EQUIPMENT |
| | AND APPLIANCE SIZING. |
| | |
| | 4. TWO SEPERATE 20 AMP CIRCUTS ARE PROPOSED FOR NEW |
| | MINI-SPLIT SYSTEM. PROVIDE MANUFACTURERS SPCIFICATIONS |
| | TO VERIFY POWER REQUIREMENTS. M1401.1 INSTALLATION |
| | |
| | 5. PROVIDE SURVEY. SHOW LOCATION OF NEW CONDENSING |
| | UNIT. PROVIDE DISTANCE TO PROPERTY LINE. 107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 6. PROVIDE NOTE ON PLAN TO PROVIDE LOCKING ACCESS |
| | PORTS. M1411.8 LOCKING ACCESS PORT CAPS. |
| | |
| | 7. PROVIDE DETAIL OF CONDENSATE DISPOSAL PIPING ROUTING |
| | THROUGH BUILDING. M1411.3 CONDENSATE DISPOSAL. |
| | |
| | 8. PROVIDE A 125-VOLT, SINGLE PHASE, 15 OR 20 AMP |
| | RECEPTACLE OUTLET FOR THE SERVICING OF THE NEW |
| | MECHANICAL EQUIPMENT. E3901.12 HVAC OUTLET. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY |
| | REVIEWED SHEETS DETACHED. |
| | |
| | |