| 2019-04-08 17:37:26 | ELECTRICAL PLAN REVIEW |
| | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | BUILDING PLANS EXAMINER, PX3169 |
| | 1&2 FAMILY PLANS EXAMINER, SFP306 |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | 2ND REVIEW |
| | RESULTS: DENIED |
| | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED |
| | BELOW. |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | 1. THE PALM BEACH COUNTY PROPERTY APPRAISERS OFFICE |
| | LIST THIS BLDG. AS A 2 STORY MULTI-FAMILY RESIDENTIAL |
| | STRUCTURE WITH 2 UNITS. BUILDING DATA INFO. ON PLAN |
| | PAGE A-1 STATES THIS STRUCTURE IS A 2 STORY STRUCTURE |
| | WITH ONLY 1 UNIT. NO RECORDS ARE AVAILABLE THAT |
| | INDICATES THESE 2 UNITS HAVE BEEN COMBINED. PLEASE |
| | CLARIFY. IDENTIFY UNIT THIS PROPOSED SCOPE OF WORK IS |
| | FOR. IF BOTH UNITS ARE TO RECIEVE WORK, PROVIDE PLAN |
| | AND SCOPE OF WORK FOR 2ND UNIT. |
| | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 2. NEW CHANGE IN SERVICE - |
| | 2A. STATE CONDUCTOR SIZE OF EXISTING SERVICE DROP. |
| | E3602.1 AMPACITY OF UNGROUNDED CONDUCTORS. |
| | 2B. IDENTIFY LOCATION OF SERVICE DISCONNECT. E3601.6.2 |
| | SERVICE DISCONNECT LOCATION. |
| | 2C. PROVIDE LOAD CALCULATIONS FOR BOTH NEW PANELS. |
| | UTILIZE RESIDENTIAL FORMULA TABLE E3602.2 |
| | 2D. PROVIDE AIC CALCULATIONS FOR BOTH NEW SERVICES. |
| | E3602.2 SERVICE LOAD. |
| | |
| | 3. ELECTRICAL NOTE #6 IS INCORRECT. AFCI PROTECTION IS |
| | REQUIRED PER THE FOLLOWING: E3902.16 ARC-FAULT |
| | CIRCUIT-INTERRUPTER PROTECTION. |
| | BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15- |
| | AND 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY |
| | ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, |
| | DENS, BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS, |
| | HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS |
| | SHALL BE PROTECTED BY ANY OF THE FOLLOWING: [210.12(A)] |
| | |
| | 4. ELECTRICAL PLAN SHOWS BOTH KITCHEN COUNTER TOP |
| | RECEPTACLES ARE SUPPLIED FROM A SINGLE 20AMP CIRCUT- |
| | #2. PLEASE SEE FBC R3703.2 AND CORRECT. |
| | E3703.2 KITCHEN AND DINING AREA RECEPTACLES. |
| | A MINIMUM OF TWO 20-AMPERE-RATED BRANCH CIRCUITS SHALL |
| | BE PROVIDED TO SERVE ALL WALL AND FLOOR RECEPTACLE |
| | OUTLETS LOCATED IN THE KITCHEN, PANTRY, BREAKFAST AREA, |
| | DINING AREA OR SIMILAR AREA OF A DWELLING. THE KITCHEN |
| | COUNTERTOP RECEPTACLES SHALL BE SERVED BY A MINIMUM OF |
| | TWO 20-AMPERE-RATED BRANCH CIRCUITS, EITHER OR BOTH OF |
| | WHICH SHALL ALSO BE PERMITTED TO SUPPLY OTHER |
| | RECEPTACLE OUTLETS IN THE SAME KITCHEN, PANTRY, |
| | BREAKFAST AND DINING AREA INCLUDING RECEPTACLE OUTLETS |
| | FOR REFRIGERATION APPLIANCES. [210.11(C)(1) AND |
| | 210.52(B)(1) AND (B)(2)]. |
| | |
| | 5. CIRCUT #10 OVERCURRENT PROTECTION AND CONDUCTOR SIZE |
| | IS INCORRECT. E3703.4 BATHROOM BRANCH CIRCUITS AND |
| | TABLE E3702.14. |
| | A MINIMUM OF ONE 20-AMPERE BRANCH CIRCUIT SHALL BE |
| | PROVIDED TO SUPPLY BATHROOM RECEPTACLE OUTLET(S). SUCH |
| | CIRCUITS SHALL HAVE NO OTHER OUTLETS. [210.11(C)(3)]. |
| | |
| | 6. PANEL SCHEDULE ON PLAN PAGE A-1 IS LABELED WINDOW |
| | AND DOOR SCHEDULE. PLEASE CORRECT. 107.2.1 INFORMATION |
| | ON CONSTRUCTION DOCUMENTS. |
| | |
| | 7. OVERCURRENT PROTECTION FOR THE INDOOR AND OUTDOOR |
| | MINI-SPLIT A/C SYSTEM PROPOSES TWO SEPERATE SINGLE POLE |
| | 20AMP CIRCUTS. PROVIDE MANUFACTURERS SPCIFICATIONS TO |
| | VERIFY. E3702.11 BRANCH CIRCUITS FOR AIR-CONDITIONING |
| | AND HEAT PUMP EQUIPMENT. |
| | |
| | 8. PROVIDE A 125-VOLT, SINGLE PHASE, 15 OR 20 AMP |
| | RECEPTACLE OUTLET FOR THE SERVICING OF THE NEW |
| | MECHANICAL EQUIPMENT. E3901.12 HVAC OUTLET. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY |
| | REVIEWED SHEETS DETACHED. |
| | |
| | |
| | |
| | |
| | |