| 2018-12-06 15:11:38 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) THE SUBMITTED PLAN SHEET SHOWS VERY GENERAL |
| | INFOMATION WITH A LARGE CLOUD AREA. |
| | |
| | THE PREVIOUS PLANS SHOWED A DOMESTIC PUMP AREA. |
| | |
| | WHAT HAPPENED TO THE THAT PUMP? |
| | |
| | |
| | |
| | 2) THERE ARE INDICATIONS WHERE THE NEW PIPING HAS |
| | BREACHED A FIRE RATED WALL. |
| | |
| | PLEASE PROVIDE THE LISTED FIRE WALL PENETRATIONS USED |
| | TO MAINTAIN THIS RATING? |
| | |
| | |
| | |
| | 3) THERE IS AN INDICATION "DOOR TO BE REMOVED" AND A |
| | NEW DOOR ADDED. |
| | |
| | THE PUMP ROOM IS REQUIRED TO BE RATED. IS THIS NEW DOOR |
| | RATED? |
| | |
| | HOW IS IT ASCESSED? |
| | |
| | WAS AN EXIT LIGHT MOVED OR PROVIDED? |
| | |
| | HOW WAS THE DOOR VOID SPACE INFILLED? |
| | |
| | PLEASE CORRECT OR PROVIDE SPECIFIC DETAILES AND FIRE |
| | CODE REFERENCES. |
| | |
| | |
| | |
| | 4) THERE IS TWO NEW PIPES ENTERING ANOTHER ROOM AND |
| | BREACHING ANOTHER WALL. |
| | |
| | THIS NEW ROOM IS NOT INDICATED AND HOW IT IS BEING |
| | USED. |
| | |
| | PLEASE PROVIDE THE ROOM DETAIL AND HOW IT IS USED.. |
| | |
| | |
| | |
| | 5) THE FDC CONFIGURATION IS DIFFERENT THAN PREVIOUSLY |
| | SUBMITTED. |
| | |
| | IT APPEARS THE FDC IS FEEDING THE INCORRECT END |
| | (DISCHARGE) OF THE PUMP. |
| | |
| | PLEASE REVIEW AND CORRECT OR EXPLAIN WITH DETAILS. |
| | |
| | |
| | |
| | 6) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | |
| | 7) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |
| | |