2018-12-27 14:42:151) SUBMIT TWO COPIES OF MANUFACTURER'S SPECIFICATIONS
 AND INSTALLATION MANUAL FOR THE COMPRESSOR AND OTHER
 SYSTEM COMPONENTS. WPB AMEND. TO FBC SEC. 107.2.1.
 2) SHT. P-3 - IDENTIFY ALL SYSTEM COMPONENTS ON THE CEP
 BUILDING - NEW AIR COMPRESSOR PLAN, INCLUDING THE
 EXISTING. WPB AMEND. TO FBC SEC. 107.2.1.
 3) SHT. E-1 - PROVIDE THE UL ASSEMBLY NUMBER FOR THE 2
 HOUR FIRE RATED FIRESTOP SYSTEM FOR MULTIPLE METAL PIPE
 THROUGH CONCRETE WALLS. THERE IS NO UL ASSEMBLY NUMBER
 ON THE DETAIL.
 4) SUBMIT A COMPRESSED AIR PIPING RISER FOR ANY NEW
 PIPING TO BE ADDED. SHOW THE REQUIRED THERMOMETER AND
 PRESSURE GAUGE ON THE DISCHARGE PIPING FROM EACH AIR
 COMPRESSOR AND RECEIVER PER THE SPECIFICATIONS ON SHT.
 P-1. SHOW ALL REQUIRED VALVES PER THE SPECIFICATIONS.
 WPB AMEND. TO FBC SEC. 107.2.1.
 5) SUBMIT ADDITIONAL INFORMATION FOR THE ANCHORING OF
 THE COMPRESSOR TO THE SLAB/PAD. THE PLANS CALL OUT 5/8"
 BOLTS. INDICATE THE LENGTH OF THE BOLTS AND TORQUING
 REQS. FOR THE BOLTS. WPB AMEND. TO FBC SEC. 107.2.1.
 6) SHT. P-4 - SOME OF THE PRINTING ON THE DETAILS IS SO
 SMALL IT IS ILLEGIBLE. SUBMIT DETAILS WHERE THE THE
 NOTES ARE LEGIBLE. WPB AMEND. TO FBC SEC. 107.2.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW