| 2018-12-27 14:42:15 | 1) SUBMIT TWO COPIES OF MANUFACTURER'S SPECIFICATIONS | | | AND INSTALLATION MANUAL FOR THE COMPRESSOR AND OTHER | | | SYSTEM COMPONENTS. WPB AMEND. TO FBC SEC. 107.2.1. | | | 2) SHT. P-3 - IDENTIFY ALL SYSTEM COMPONENTS ON THE CEP | | | BUILDING - NEW AIR COMPRESSOR PLAN, INCLUDING THE | | | EXISTING. WPB AMEND. TO FBC SEC. 107.2.1. | | | 3) SHT. E-1 - PROVIDE THE UL ASSEMBLY NUMBER FOR THE 2 | | | HOUR FIRE RATED FIRESTOP SYSTEM FOR MULTIPLE METAL PIPE | | | THROUGH CONCRETE WALLS. THERE IS NO UL ASSEMBLY NUMBER | | | ON THE DETAIL. | | | 4) SUBMIT A COMPRESSED AIR PIPING RISER FOR ANY NEW | | | PIPING TO BE ADDED. SHOW THE REQUIRED THERMOMETER AND | | | PRESSURE GAUGE ON THE DISCHARGE PIPING FROM EACH AIR | | | COMPRESSOR AND RECEIVER PER THE SPECIFICATIONS ON SHT. | | | P-1. SHOW ALL REQUIRED VALVES PER THE SPECIFICATIONS. | | | WPB AMEND. TO FBC SEC. 107.2.1. | | | 5) SUBMIT ADDITIONAL INFORMATION FOR THE ANCHORING OF | | | THE COMPRESSOR TO THE SLAB/PAD. THE PLANS CALL OUT 5/8" | | | BOLTS. INDICATE THE LENGTH OF THE BOLTS AND TORQUING | | | REQS. FOR THE BOLTS. WPB AMEND. TO FBC SEC. 107.2.1. | | | 6) SHT. P-4 - SOME OF THE PRINTING ON THE DETAILS IS SO | | | SMALL IT IS ILLEGIBLE. SUBMIT DETAILS WHERE THE THE | | | NOTES ARE LEGIBLE. WPB AMEND. TO FBC SEC. 107.2.1. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | |
|