2019-04-19 15:14:50****CORRECTIONS****
 W.P.B. PERMIT: 1901
 REVIEWED: APRIL 19, 2019
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER PX4191
 [email protected]
 561-805-6718
  
 FBC[AMENDED] = FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC[E] = FBC ENERGY CONSERVATION
 FBC[R] = FBC RESIDENTIAL
  
 1) ALONG WITH PROVIDING CLASS I VAPOR BARRIER ITEM 2 OF
 R408.3 NEEDS TO BE ADDRESSED.
 R408.3 UNVENTED CRAWL SPACE. VENTILATION OPENINGS IN
 UNDERFLOOR SPACES SPECIFIED IN SECTIONS R408.1 AND
 R408.2 SHALL NOT BE REQUIRED WHERE THE FOLLOWING ITEMS
 ARE PROVIDED:
 1. EXPOSED EARTH IS COVERED WITH A CONTINUOUS CLASS I
 VAPOR RETARDER. JOINTS OF THE VAPOR RETARDER SHALL
 OVERLAP BY 6 INCHES (152 MM) AND SHALL BE SEALED OR
 TAPED. THE EDGES OF THE VAPOR RETARDER SHALL EXTEND NOT
 LESS THAN 6 INCHES (152 MM) UP THE STEM WALL AND SHALL
 BE ATTACHED AND SEALED TO THE STEM WALL OR INSULATION.
 2. ONE OF THE FOLLOWING IS PROVIDED FOR THE UNDER-FLOOR
 SPACE: 2.1. CONTINUOUSLY OPERATED MECHANICAL EXHAUST
 VENTILATION AT A RATE EQUAL TO 1 CUBIC FOOT PER MINUTE
 (0.47 L/S) FOR EACH 50 SQUARE FEET (4.7 M2) OF CRAWL
 SPACE FLOOR AREA, INCLUDING AN AIR PATHWAY TO THE
 COMMON AREA (SUCH AS A DUCT OR TRANSFER GRILLE), AND
 PERIMETER WALLS INSULATED IN ACCORDANCE WITH THE
 FLORIDA BUILDING CODE, ENERGY CONSERVATION.
 2.2. CONDITIONED AIR SUPPLY SIZED TO DELIVER AT A RATE
 EQUAL TO 1 CUBIC FOOT PER MINUTE (0.47 L/S) FOR EACH 50
 SQUARE FEET (4.7 M2) OF UNDER-FLOOR AREA, INCLUDING A
 RETURN AIR PATHWAY TO THE COMMON AREA (SUCH AS A DUCT
 OR TRANSFER GRILLE), AND PERIMETER WALLS INSULATED IN
 ACCORDANCE WITH THE FLORIDA BUILDING CODE, ENERGY
 CONSERVATION.
 2.3. PLENUM IN EXISTING STRUCTURES COMPLYING WITH
 SECTION M1601.5, IF UNDER-FLOOR SPACE IS USED AS A
 PLENUM.
  
 2) PLEASE SELECT THE SYSTEM BEING USED ON FLAT ROOF
 PRODUCT APPROVAL AND PROVIDE RAS 177 IF APPLICABLE.
 [RAS 117]PROVIDE ENGINEERING FOR ENHANCED NAILING AS
 STATED IN PRODUCT APPROVAL UNDER GENERAL LIMITATIONS
 #7.
 THIS CAN BE DEFERRED UNTIL ROOFING SUB PERMIT IS
 APPLIED FOR, OR SUPPLIED NOW.
  
 3) ALL OTHER COMMENTS ADDRESSED.