| 2019-01-02 15:57:20 | 01/02/2019 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS | | | | | | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS | | | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE | | | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. | | | | | | 1. ACCORDING TO MANUFACTURES SPECIFICATION ON AN AIR | | | ADMITTANCE VALVE FOR THE WASHING MACHINE, IT NEEDS TO | | | BE A 3? STANDPIPE, 2017 FBC SEC R P3114.2 INSTALLATION. | | | 2. STANDPIPE ISOMETRIC DRAWING S-7 REQUIRES A TRAP THEN | | | VENT TO AAV, 2017 FBC SEC. R3101.2 TRAP SEALS | | | PROTECTION. | | | 3. HOT WATER UNDERGROUND REQUIRES R-13 INSULATION | | | ACCORDING TO 2017 FBC SEC. RE 403.5.3. | | | 4. IF THE SHOWER PAN IS NOT RECEDED IT WILL REQUIRE | | | LINING, 2017 FBC SEC. R 2709.2. | | | | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS | | | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | | | | LUIS A. CRESPO | | | PLUMBING INSPECTOR / | | | PLUMBING PLAN REVIEW | | | AVAILABLE FROM 1:00 PM TO 4:00 PM | | | [email protected] | | | 561-805-6720 | | | | | | |
|