Plan Review Notes
Plan Review Notes For Permit 18111203
Permit Number 18111203
Review Stop P
Sequence Number 1
Notes
Date Text
2019-01-02 15:57:2001/02/2019 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. ACCORDING TO MANUFACTURES SPECIFICATION ON AN AIR
 ADMITTANCE VALVE FOR THE WASHING MACHINE, IT NEEDS TO
 BE A 3? STANDPIPE, 2017 FBC SEC R P3114.2 INSTALLATION.
 2. STANDPIPE ISOMETRIC DRAWING S-7 REQUIRES A TRAP THEN
 VENT TO AAV, 2017 FBC SEC. R3101.2 TRAP SEALS
 PROTECTION.
 3. HOT WATER UNDERGROUND REQUIRES R-13 INSULATION
 ACCORDING TO 2017 FBC SEC. RE 403.5.3.
 4. IF THE SHOWER PAN IS NOT RECEDED IT WILL REQUIRE
 LINING, 2017 FBC SEC. R 2709.2.
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6720
  
  