Plan Review Notes
Plan Review Notes For Permit 18111203
Permit Number 18111203
Review Stop M
Sequence Number 1
Notes
Date Text
2019-01-03 09:17:07MECHANICAL PLAN REVIEW FAIL
  
 1 NEED RETURN DUCTS IN BEDROOMS PER 2017 FLORIDA
 BUILDING CODE - RESIDENTIAL SEC. 2017 FLORIDA BUILDING
 CODE - RESIDENTIAL
  
 2 PLEASE EXPLAIN DESIGN - HOW IS FLEX DUCT ATTACHED TO
 FLEX DUCT - NEED SIZE ON ALL DUCTS PER 2017 FLORIDA
 BUILDING CODE - BUILDING SEC. [A]107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
  
 CHRIS MONTELLO
 561-805-6733