Plan Review Notes
Plan Review Notes For Permit 18111203
Permit Number 18111203
Review Stop E
Sequence Number 1
Notes
Date Text
2018-12-14 15:49:17CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. NOTE 25 AND NOTE IN SYMBOLS LEGEND STATES THAT
 RECEPTACLES SHALL BE TAMPER RESISTANT PER NEC 406.11.
 THIS CODE SECTION DOES NOT APPLY TO TAMPER RESISTANT
 RECEPTACLES. PROVIDE CORRECTION. NEC 406.12; FBC RE
 E4002.14
 2. PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL
 LOADS. NEC 220; FBC RE E3602.2
 3. A MINIMUM OF TWO SMALL APPLIANCE BRANCH CIRCUITS IS
 REQUIRED FOR KITCHEN COUNTER TOP RECEPTACLE OUTLETS.
 THE LIGHTING IN THE KITCHEN IS NOT PERMITTED TO BE ON
 ONE OF THE SMALL APLLIANCE CIRCUITS. PROVIDE
 CORRECTION. NEC 210.11(C)(1) , FBC RE E3703.2
 4. THE DRYER LOAD IS NOT SHOWN IN PANEL SCHEDULE OR
 LOAD CALCULATION. PROVIDE CORRECTION. NEC 220.54; FBC
 RE E3602.2
 5. ITEMS MARKED WITH AN ASTERIK IN PANEL SCHEDULE FOR
 AFCI PROTECTION DO NOT INCLUDE ALL AREAS REQUIRED TO BE
 AFCI PROTECTED. ALL BRANCH CIRCUITS THAT SUPPLY
 120-VOLT, SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS
 INSTALLED IN KITCHENS, FAMILY ROOMS, DINING ROOMS,
 LIVING ROOMS, PARLORS, LIBRARIES, DENS, BEDROOMS,
 SUN-ROOMS, RECREATIONS ROOMS, CLOSETS, HALLWAYS,
 LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS SHALL BE AFCI
 PROTECTED. THIS INCLUDES LIGHTING AND POWER OUTLETS AND
 RECEPTACLES. SOME AREAS REQUIRE BOTH AFCI AND GFCI
 PROTECTION. PROVIDE CORRECTION. NEC 210.8, 210.12; FBC
 RE E3902; FBC EX 607.1.1 OR 801.1, 801.2, OR 901.2 AS
 APPLICABLE.
 6. PROVIDE CARBON MONOXIDE ALARMS WITHIN 10 FEET OF
 EACH ROOM USED FOR SLEEPING PURPOSES. FBC RE R315.1
 7. SMOKE ALARMS MUST BE INSTALLED AT LEAST 3 FEET FROM
 BATHROOM DOOR, 3 FEET FROM CEILING FANS, AND 3 FEET
 FROM ANY MECHANICAL DUCT. PROVIDE CORRECTIONS. FBC RE
 R314.3(4), NFPA 72:29.8.3.4
 8. SMOKE ALARMS SHOULD NOT BE INSTALLED WITHIN CERTAIN
 DISTANCES FROM THE RANGE, DEPENDING ON THE TYPE OF
 SMOKE ALARM USED. SEE FBC RE R314.3.1 AND PROVIDE
 CORRECTION.
 9. ALL KITCHEN COUNTER RECEPTACLE OUTLETS ARE REQUIRED
 TO BE GFCI PROTECTED ON AN AFCI CIRCUIT. PROVIDE
 CORRECTION. NEC 210.8, 210.12; FBC RE E3902
 10. A GFCI PROTECTED RECEPTACLE OUTLET ON A 20 AMP
 CIRCUIT IS REQUIRED WITHIN 3 FEET OF EACH BASIN.
 PROVIDE CORRECTION FOR MASTER BATH. NEC 210.11(C)(3),
 210.52(D); FBC RE E3703.4, E3901.6
 11. PLAN SHOWS #8 WIRE ON A 50 AMP BREAKER FOR THE
 RANGE. #8 ROMEX WIRE, WHICH IS TYPICAL IN RESIDENTIAL
 WIRING, IS NOT RATED FOR 50 AMPS. PROVIDE CORRECTION.
 NEC 334.80; FBC RE E3705.4.4
 12. A GFCI PROTECTED RECEPTACLE OUTLET IS REQUIRED ON
 THE ISLAND. PROVIDE CORRECTION. NEC 210.8,
 210.52(C)(2); FBC RE E3901.4.2
 13. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT
 SERVICE. SHOW ON PLAN. NEC 250.94; FBC RE E3609.3
 14. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR
 SERVICE PANEL INCLUDING INFORMATION FROM THE POWER
 COMPANY STATING WHAT THE AVAILABLE SHORT CIRCUIT
 CURRENT IS FOR THE SERVICE TO CONFIRM THE STATED AIC
 RATING OF THE SERVICE EQUIPMENT IS ADEQUATE. NEC 110.9,
 110.10; FBC RE E3606.3
 15. PROVIDE AIC RATING OF SERVICE PANEL. NEC 110.3,
 110.9; FBC RE E3606.3
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  