Plan Review Notes
Plan Review Notes For Permit 18111203
Permit Number 18111203
Review Stop B
Sequence Number 1
Notes
Date Text
2019-01-02 11:13:59****CORRECTIONS****
 W.P.B. PERMIT: 18111203
 REVIEWED: JANUARY 02, 2019
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER I
 [email protected]
 561-805-6718
  
 FBC[AMENDED] = FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC[B] = FBC BUILDING
 FBC[EXISTING] = FBC EXISTING BUILDING
 FBC[A] = FBC ACCESSIBILITY
 FBC[E] = FBC ENERGY CONSERVATION
 FBC[R] = FBC RESIDENTIAL
  
 1) 103.1.1.2 FBC[E] THE BUILDING'S OWNER, THE OWNER'S
 ARCHITECT OR OTHER AUTHORIZED AGENT LEGALLY DESIGNATED
 BY THE OWNER SHALL CERTIFY THAT THE BUILDING IS IN
 COMPLIANCE WITH THE CODE, AS PER SECTION 553.907,
 FLORIDA STATUTES, PRIOR TO RECEIVING THE PERMIT TO
 BEGIN CONSTRUCTION OR RENOVATION. 553.907, FLORIDA
 STATUTES. -PLEASE HAVE THE OWNER SIGN THE ENERGY
 CALCULATIONS
  
 2) 107.5.3[E] THE FLOOR TYPE IN THE ENERGY CALCULATIONS
 SAYS SLAB ON GRADE. THIS IS A RAISED WOOD FLOOR.
 -UPDATE ENERGY CALCULATIONS FOR THE EXISTING FLOOR TYPE
 AND R-VALUE)
  
 3) 408.1 [R] VENTILATION. THE UNDER-FLOOR SPACE BETWEEN
 THE BOTTOM OF THE FLOOR JOISTS AND THE EARTH UNDER ANY
 BUILDING (EXCEPT SPACE OCCUPIED BY A BASEMENT) SHALL
 HAVE VENTILATION OPENINGS THROUGH FOUNDATION WALLS OR
 EXTERIOR WALLS.
 -PLEASE PROVIDE THE AMOUNT OF EXISTING UNDER FLOOR
 VENTILATION AND SHOW WHERE ACCESS PANEL IS LOCATED.
  
  
 4) 806.5 [R] UNVENTED ATTIC AND UNVENTED ENCLOSED
 RAFTER ASSEMBLIES.
 5.1.2. WHERE AIR-PERMEABLE INSULATION IS PROVIDED
 INSIDE THE BUILDING THERMAL ENVELOPE, IT SHALL BE
 INSTALLED IN ACCORDANCE WITH SECTION 5.1.1. IN ADDITION
 TO THE AIR-PERMEABLE INSULATION INSTALLED DIRECTLY
 BELOW THE STRUCTURAL SHEATHING, RIGID BOARD OR SHEET
 INSULATION SHALL BE INSTALLED DIRECTLY ABOVE THE
 STRUCTURAL ROOF SHEATHING IN ACCORDANCE WITH THE
 R-VALUES IN TABLE R806.5 FOR CONDENSATION CONTROL.
 -PLEASE REVIEW THIS SECTION FOR AIR PERMEABLE
 INSULATION AT ROOF DECK.
  
 5) 107 5.3 [AMENDED] PROVIDE PRODUCT APPROVAL FOR HARDI
 PLANK SIDING AND STATE ATTACHMENT TYPE AND SPACING, OR
 INDICATE THAT THE SUBMITTAL WILL BE DEFERRED.
  
 6) 905.11.1 [R] SLOPE. MODIFIED BITUMEN MEMBRANE ROOFS
 SHALL
 HAVE A DESIGN SLOPE OF NOT LESS THAN ONE-FOURTH UNIT
 VERTICAL
 IN 12 UNITS HORIZONTAL (2-PERCENT SLOPE) FOR DRAINAGE.
 -UPDATE SHEET S-06 TO SHOW MINIMUN SLOPE AS REQ?D
 905.11.1 [R].
  
 7) [FBC AMENDED 107.3.4.1]PROVIDE PRODUCT APPROVAL FOR
 LOW SLOPE ROOFING, OR INDICATE THAT YOU WOULD LIKE IT
 DEFERED.
  
 NOTE:
 -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
 -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF MATERIALS REQUESTED.
 -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  