| 2018-12-03 18:49:32 | PLAN REVIEW COMMENTS |
| | |
| | 1ST REVIEW: FBC FIFTH EDITION (2014) |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY BUILDING |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) SYSTEM A - PRODUCT APPROVAL FL16730-R17, FOR THE |
| | EVERGUARD TPO SINGLE-PLY ROOF MEMBRANE SYSTEM SYSTEM |
| | NUMBER S-106 ON PAGE 26 OF 86 HAS A MAXIMUM DESIGN |
| | PRESSURE OF -45.0 PSF AND IS MARKED WITH AN ASTERISK. |
| | ACCORDING TO NOTE #9 ON PAGE 3 OF 86 INCREASED FASTENER |
| | DENSITY EXTRAPOLATION IS NOT PERMITTED FOR SYSTEMS THAT |
| | ARE MARKED WITH AN ASTERISK *. SUBMIT ROOFING PRODUCT |
| | APPROVALS WITH ADEQUATE DESIGN PRESSURES. FBC 1609.1 |
| | |
| | 2) THE PRODUCT APPROVALS THAT WERE SUBMITTED HAVE NOT |
| | BEEN APPROVED IN WRITING BY THE DESIGNER OF RECORD FOR |
| | THIS PROJECT. FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT |
| | APPROVALS FOR THOSE PRODUCTS WHICH ARE REGULATED BY FAC |
| | 61G20-3.001 PER FLORIDA STATUTE 553.842 (5) THAT HAVE |
| | BEEN REVIEWED AND APPROVED IN WRITING BY THE DESIGNER |
| | OF RECORD. PROVIDE TWO COMPLETE PRODUCT APPROVALS WITH |
| | FL OR NOA NUMBERS INCLUDING INSTALLATION INSTRUCTIONS |
| | AND MAXIMUM DESIGN PRESSURES FOR EACH OF THE DIFFERENT |
| | ROOFING MATERIALS, WINDOW (GLASS TYPES), STRUCTURAL |
| | MULLIONS AND EXTERIOR DOOR TYPES. |
| | |
| | 3) THREE SETS OF CONSTRUCTION DOCUMENTS ARE TYPICALLY |
| | SUBMITTED FOR THRESHOLD BUILDINGS. IF YOU WISH TO HAVE |
| | A SET OF PLANS FOR THE THRESHOLD INSPECTOR, YOU WILL |
| | HAVE TO SUBMIT AN ADDITIONAL SET OF DOCUMENTS. FBC |
| | 107.1 |
| | |
| | |