| 2018-12-28 16:25:26 | 1ST REVIEW FBC-2017 MECHANICAL | | | MASTER PERMIT #18040104 | | | REVISION #18111193 | | | 12/28/18 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | | 2017 | | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | | 2017 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | | EDITION 2017 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET M2.2: THE 6X4 DUCT IS NOT PERMITTED TO | | | PENETRATE INTO THE INTERIOR EXIT STAIRWAY B- SECTION | | | 1023.5 FBC B. | | | | | | 2) M2.2: A FIRE DAMPER IS REQUIRED AT THE PENETRATION | | | OF THE 12X12 DUCT THROUGH THE FLOOR INTO THE BASEMENT- | | | SECTION 607.6.1 FBC M. | | | | | | 3) M2.4A: REVISE THE O/A CALCULATIONS AND THE AC | | | EQUIPMENT SCHEDULE ON THE MAIN PLAN TO INCLUDE THE NEW | | | THIRD FLOOR AC SYSTEMS- SECTION 107.2.1 WPB. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|