| Plan Review Notes For Permit 18111160 |
| Permit Number |
18111160 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-11-29 18:59:10 | RE-ROOF BUILDING REVIEW COMMENTS | | | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. | | | | | | 1- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY | | | FAC 61G20-3.001 FOR THE FLAT ROOF SYSTEM TO BE USED. | | | AND, CLEARLY MARK WHICH APPROVED ASSEMBLY IS GOING TO | | | BE INSTALLED TO VERIFY COMPLIANCE WITH THE DESIGN | | | PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL. NOTE: IF THE | | | SELECTED ASSEMBLY DOESN'T MEET THE DESIGN PRESSURES FOR | | | ALL ROOF ZONES, THEN SIGNED AND SEALED RAS 117 | | | CALCULATIONS ARE REQUIRED. | | | | | | 2- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO | | | LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS, | | | CONTRACTOR'S OVERHEAD AND PROFIT AND DESIGN | | | PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY | | | AMENDMENTS. UPDATE VALUATION OR PROVIDE COPY OF SIGNED | | | CONTRACTS INCLUDING DESIGN PROFESSIONAL FEES. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] | | | |
|