| Date |
Text |
| 2018-11-29 18:43:14 | RE-ROOF BUILDING REVIEW COMMENTS |
| | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| | |
| | 1- REVISE RAS 117 CALCULATIONS SUBMITTED; |
| | A) CALCULATIONS SUBMITTED SPECIFY 8'-0" HEIGHT FOR THIS |
| | BUILDING. THIS IS INCORRECT. THIS IS A TWO STORY |
| | BUILDING. PROVIDE THE CORRECT MEAN ROOF HEIGHT AND |
| | REVISE DESIGN PRESSURES ACCORDINGLY. SEC. 1609.1 FBC |
| | AND CITY POLICY FOR ALL ROOFING PERMITS. |
| | |
| | B) NUMBER OF BASE SHEET FASTENING ROWS SPECIFIED (3) |
| | ARE INCORRECT BASED ON THE SPECIFIED DESIGN PRESSURES. |
| | BY RUNNING RAS 117 CALCULATIONS BASED ON THE DESIGN |
| | PRESSURES AND NAILING SPACING SHOWN FOR ROOF ZONE #1 I |
| | FOUND THAT NEED AT LEAST 5 ROWS IN THE FIELD OF THE |
| | SHEET FOR ROOF ZONE #3. REVISE AS REQUIRED. NOTE: RAS |
| | 117 CALCULATIONS SEC. 8.1 DOESN'T ALLOW NAIL SPACING |
| | LESS THAN 4"O.C. THAT'S WHY 5 ROWS ARE REQUIRED. |
| | |
| | C) FLAT ROOF NOA 15-1020.01 DOESN'T MATCH NOA |
| | 18-0919.12 SUBMITTED. REVISE AS REQUIRED TO MATCH. SEC. |
| | 107.2.1 CITY AMENDMENTS. |
| | |
| | D) THERE ARE TWO BUILDING THIS PROPERTY. CLARIFY IF |
| | RE-ROOFING BOTH BUILDINGS OR JUST ONE. BASED ON |
| | PROPERTY APPRAISER THE SQUARE FOOTAGE IS +/- 5784 S.F. |
| | FOR BOTH BUILDING. VALUATION WAS UPDATED TO $36,150 AS |
| | REQUIRED BY SEC. 109.3 CITY AMENDMENTS. THE PERMIT FEE |
| | BALANCE IS $808.86. |
| | OR PROVIDE COPY OF SIGNED CONTRACT (BOTH PARTIES) FOR |
| | BUILDING OFFICIAL CONSIDERATION. |
| | |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE/VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | PLEASE DON'T STAPLE OLD DOCUMENTS. SUBMIT OLD DOCUMENTS |
| | FOR REFERENCE. |
| | |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | (561)805-6712 |
| | [email protected] |
| | |