| Notes |
| Date |
Text |
| 2018-12-03 11:32:00 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | | | | 1) THERE ARE PLAN ATTACHED SHOWING LOCATION OR HOW | | | MANY. | | | | | | PLEASE PROVIDE A SITE PLAN INDICATING LOCATION AND | | | NUMBER. | | | | | | | | | | | | 2) THERE ARE SPECIFICATION SHEETS ATTACHED INDICATING | | | WHAT KIND AND LISTINGS. | | | | | | PLEASE PROVIDE MANUFACTURES SPECIFICATION SHEETS. | | | | | | | | | | | | 3) THERE ARE NO INDICATIONS OF COMPLIANCE WITH ANY FIRE | | | CODES. | | | | | | ALL INSTALLTION SHALL COMPLY WITH ALL LOCAL AND | | | NATIONAL CODES INDCULEING, BUT NOT LIMITED TO, | | | | | | FLAMMABLE AND COMBUSTIBLE LIQUIDS SHALL COMPLY WITH | | | NFPA 30, 2015 EDITION | | | MOTOR FUEL DISPENSING FACILITIES AND REPAIR GARAGES | | | SHALL COMPLY WITH NFPA 30 A, 2015 EDITION | | | | | | PLEASE PROVIDE AN APPLICABLE NOTE TO THE RE-SUBMITTED | | | PLAN SETS. | | | | | | | | | | | | | | | 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | | | | 5)ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|