| 2019-03-08 08:24:28 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #18111103 |
| | 3/8/19 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) IN REFERENCE TO COMMENT #1 FROM THE 1ST REVIEW, THE |
| | REQUESTED MSDS SHEETS FOR THE MATERIALS BEING TESTED |
| | WERE NOT SUBMITTED. |
| | |
| | 2) IN REFERENCE TO COMMENT #5 FROM THE 1ST REVIEW, |
| | PLEASE SUBMNIT MANUFACTURER'S SPECIFICATIONS FOR THE |
| | SLOW COOKER. |
| | |
| | 3) NEW COMMENT, SHEET M-1: SMOKE DETECTORS ARE REQUIRED |
| | IN THE SUPPLY AIR SYSTEMS OF EACH 5-TON AC SYSTEM PER |
| | SECTION 606.2.1 FBC M. PLEASE NOTE THAT AN EXEMPTION |
| | CAN BE APPLIED IF THE MANUFACTURER'S SPECIFICATIONS |
| | INDICATE THE SYSTEMS ARE NOT CAPABLE OF PRODUCING OVER |
| | 2000 CFMS OF SUPPLY AIR. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |