| 2019-03-07 12:31:38 | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 18111103 |
| | ADD: 901 NORTHWOOD PARKWAY, SUITE: 202-205 |
| | CONT: TBD/ TO BE DETERMINED |
| | TEL: 561-373-3902 |
| | E-MAIL: [email protected] |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | DATE: 03/06/19 |
| | ACTION: DENIED |
| | |
| | |
| | NOTE: |
| | BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO |
| | MEANS CONTRACTOR WILL SUBMIT REQUIRED INFORMATION AFTER |
| | THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO AVOID |
| | CONFLICTS/DELAYS. REVISION FEES MAY APPLY. CONTRACTOR |
| | TO ADVICE IF PROVISO OPTION IS PREFERRED AT THIS TIME |
| | OR IF RE-SUBMITTING REQUIRED INFORMATION BEFORE PERMIT |
| | ISSUANCE. |
| | |
| | |
| | |
| | 1) OK. |
| | |
| | ORIGINAL COMMENT: |
| | 2) THE LIFE SAFETY SHEET CHAPTER 10 SCHEDULE TYPICAL IS |
| | TAKING CREDIT FOR FIRE SPRINKLERS, IF THE BUILDING IS |
| | NOT FIRE SPRINKLERED THEN CORRECT THE FOLLOWING: |
| | |
| | 2A) OK. |
| | 2B) OK. |
| | 2C) OK. |
| | |
| | NEW COMMENT: |
| | 2D) DEAD END CORRIDOR FOR UNSPRINKLERED BUILDING IS 20 |
| | FEET NOT 25 FEET. REVISE AS REQUIRED. SEC. 1020.4 FBC. |
| | ALSO, THERE IS NOT SEC. 1024.2 AS REFERENCED IN THE |
| | LIFE SAFETY TABLE ON SHEET LS-1. |
| | |
| | ORIGINAL COMMENT: |
| | 3) SHEET A-1 THE FLOOR PLAN: |
| | |
| | 3A) OK. |
| | |
| | 3B) OK. LAB EQUIPMENT INSTALLATION TO BE COORDINATED |
| | WITH CHIEF BUILDING INSPECTOR. |
| | |
| | 2017 FBC-B 3302.1 ALTERATIONS, REPAIRS AND ADDITIONS. |
| | REQUIRED EXITS, EXISTING STRUCTURAL ELEMENTS, FIRE |
| | PROTECTION DEVICES AND SANITARY SAFEGUARDS SHALL BE |
| | MAINTAINED AT ALL TIMES DURING ALTERATIONS, REPAIRS OR |
| | ADDITIONS TO ANY BUILDING OR STRUCTURE. |
| | |
| | ORIGINAL COMMENT: |
| | 3C) WALL TYPES: THE WALLS LABELED C-2 IN THE WALL |
| | SCHEDULE ARE LABELED 1 HOUR FIRE WALLS: |
| | |
| | 3C)(1) OK. |
| | 3C)(2) OK. |
| | 3D) OK. |
| | |
| | ORIGINAL COMMENT: |
| | 3E) AT THIS TIME THE OCCUPANCY OF THE LAB, CANNOT BE |
| | DETERMINED THE USAGE WILL NEED TO BE BETTER DEFINED. |
| | WHAT TYPES OF HAZARDOUS MATERIALS ARE TO BE USED IN THE |
| | DAY TO DAY USAGE OF THE LAB. PLEASE PROVIDE AMOUNT OF |
| | HAZARDOUS MATERIALS, IF THEY ARE SOLIDS, LIQUIDS, AND |
| | OR GASEOUS MATERIALS( FC-B TABLE 307.1(1), IF THEY ARE |
| | GOING TO BE STORED IN 1 HOUR FIRE RATED CABINETS, AND |
| | IF THIS ROOM (LAB) IS TO BE CONSIDERED A 1 HOUR FIRE |
| | CONTROL AREA IN COMPLIANCE WITH 2017 FBC-B SECTION |
| | 414.2 THROUGH 414.4. PLEASE ALSO SUBMIT THE MSDS SHEETS |
| | FOR ALL CHEMICALS TO BE USED IN THE DAILY PROCESS OF |
| | THE LAB. A NARRATIVE FROM THE TENANT MAYBE OF HELP OF |
| | WHAT WORK, OR PROCESS WILL OCCUR IN THE ROOM CONSIDERED |
| | A LAB. |
| | |
| | RESPONSE: |
| | PARTIALLY COMPLIED. TO AVOID CONFUSION AND TO BE CLEAR |
| | THAT CONTROL AREAS ARE NOT REQUIRED. ARCHITECT TO |
| | CLEARLY SPECIFY ON PLANS THE TYPE OF TESTING TO BE |
| | PERFORMED IN THIS LAB . AND, ACKNOWLEDGE THAT HAZARDOUS |
| | MATERIALS ARE NOT STORED OR HANDLED IN THIS LAB. ALSO, |
| | NARRATIVE FROM THE DIRECTOR OF THE LAB NEEDS TO HAVE |
| | THE SIGNATURE OF THE DIRECTOR. SEC. 107.2.1 CITY |
| | AMENDMENTS. |
| | |
| | |
| | 3F) AT THIS TIME IT IS UNCERTAIN IF THERE NEEDS TO BE |
| | OCCUPANCY SEPARATION BETWEEN THE LAB AND THE EQUIPMENT |
| | STORAGE ROOM. THE MAINTENANCE EQUIPMENT STORAGE ROOM IS |
| | 284 SQUARE FEETLESS THAN 10% OF THE FLOOR AREA OF THE |
| | BUILDING. IF PART OF THE CONTROL AREA, ADDITIONAL |
| | COMMENTS MAY OCCUR UNDER THE MECHANICAL PLAN REVIEWER. |
| | 107.2.1.2. ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | |
| | 3G) OK. |
| | |
| | ORIGINAL COMMENT: |
| | 3H)(1) SHEET A2 THE DOOR SCHEDULE INDICATES THE |
| | OVERHEAD GARAGE DOOR IS BEING REPLACED, PLEASE PROVIDE |
| | THE PRODUCT APPROVAL FOR THIS DOOR. COMPONENTS & |
| | CLADDING. 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT |
| | OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, |
| | RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS |
| | OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| | APPROVALS: |
| | |
| | (31)(A) EXTERIOR OVERHEAD GARAGE DOORS , |
| | |
| | RESPONSE: |
| | PRODUCT APPROVAL NOT SUBMITTED AT THIS TIME. |
| | THIS CAN BE A DEFERRED SUBMITTAL. |
| | |
| | |
| | ORIGINAL COMMENT: |
| | 3H)(2) W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE |
| | PRODUCTS WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE |
| | CODE RULE 61G20 SHALL BE REVIEWED AND APPROVED IN |
| | WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| | FOR JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE |
| | ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING |
| | ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC. |
| | |
| | RESPONSE: |
| | TO BE DONE AT TIME OF PRODUCT APPROVAL SUBMITTAL. |
| | |
| | |
| | ORIGINAL COMMENT: |
| | 3I) IN THE BREAK AREA/ COMMUNITY SPACE THERE IS A |
| | BARRIER FREE ELECTRIC WATER COOLER AND REFERENCES THE |
| | PLUMBING CODE SECTION 404.2. PLEASE NOTE THERE IS NO |
| | 404.2 IN THE 2017 FBC-PLUMBING CODE. YOU DO HAVE TO |
| | COMPLY WITH THE 2017 FBC-ACCESSIBILITY CODE SECTION |
| | 211.2 MINIMUM NUMBER. NO FEWER THAN TWO DRINKING |
| | FOUNTAINS SHALL BE PROVIDED. ONE DRINKING FOUNTAIN |
| | SHALL COMPLY WITH 602.1 THROUGH 602.6 AND ONE DRINKING |
| | FOUNTAIN SHALL COMPLY WITH 602.7. |
| | |
| | RESPONSE: |
| | PLANS ARE NOT SHOWING DETAILS AND SPECIFICATIONS |
| | SHOWING COMPLIANCE. PLANS ARE ONLY CITING SECTIONS OF |
| | THE FBC- ACCESSIBILITY CODE. PROVIDE COMPLETE DETAILS |
| | SHOWING COMPLIANCE. DON'T JUST CITE CODE SECTIONS. SEC. |
| | 107.2.1 CITY AMENDMENTS. |
| | |
| | |
| | 3J) OK. |
| | 3J)(1) OK. |
| | 3J)(2) OK. |
| | 3K) OK |
| | 3K)(1) OK |
| | 3K)(2)OK |
| | 3K)(3) OK |
| | 3K)(4)OK |
| | 3L) OK |
| | |
| | ORIGINAL COMMENT: |
| | 4A) BOTH THE M1 AND E1 BOTH SHOW NEW ROOF TOP UNITS |
| | PLEASE PROVIDE PRODUCT APPROVAL FOR THE NEW ROOF TOP |
| | CURB. 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT |
| | OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, |
| | RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS |
| | OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| | APPROVALS: |
| | (31)(G) ROOF TOP CURBS |
| | |
| | RESPONSE: |
| | DEFERRED SUBMITTAL |
| | |
| | 4B) W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE |
| | 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | RESPONSE: |
| | DEFERRED SUBMITTAL |
| | |
| | |
| | 4C) 2017 FBC-M- 301.15 WIND RESISTANCE. MECHANICAL |
| | EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO |
| | WIND SHALL BE DESIGNED AND INSTALLED TO RESIST THE WIND |
| | PRESSURES DETERMINED IN ACCORDANCE WITH THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | 2017 FBC-B-1609.6.4.4.1 COMPONENTS AND CLADDING. WIND |
| | PRESSURE FOR EACH COMPONENT OR CLADDING ELEMENT IS TO |
| | BE DESIGNED FOR WIND PRESSURES COMPONENTS AND |
| | ATTACHMENTS. |
| | |
| | RESPONSE: |
| | DEFERRED SUBMITTAL |
| | |
| | ORIGINAL COMMENT: |
| | 5) THE ARCHITECTURAL SHEETS DOES NOT PROVIDE ANY WIND |
| | DESIGN CRITERIA FOR THE REPLACEMENT OVERHEAD GARAGE |
| | DOOR NOR THE ROOF TOP A/C UNITS. |
| | |
| | RESPONSE: |
| | REVISE WIND DESIGN DATA ON SHEET A-2. ACCORDING TO SEC. |
| | 1609.4 THIS BUILDING IS LOCATED IN EXPOSURE "C" NO |
| | EXPOSURE "B". REVISE AS REQUIRED AND REVISE DESIGN |
| | PRESSURES ACCORDINGLY. ALSO, PROVIDE THE SIZE OF THE |
| | OVERHEAD GARAGE DOOR TO BE REPLACED TO VERIFY DESIGN |
| | PRESSURES. |
| | |
| | 2017 FBC-B 1603.1.4 WIND DESIGN DATA. |
| | THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL |
| | BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE |
| | DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE |
| | STRUCTURE: |
| | |
| | 5.1. OK. |
| | 5.2. OK. |
| | 5.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE |
| | THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2. |
| | HEIGHT AND EXPOSURE. |
| | RESPONSE: |
| | REVISE WIND EXPOSURE |
| | |
| | 5.4. OK. |
| | 5.5. OK. |
| | |
| | ORIGINAL COMMENT: |
| | 6) THE ARCHITECTURAL SHEETS DOES NOT PROVIDE ANY |
| | STRUCTURAL INFORMATION OF HOW THE ROOF TOP DECK IS TO |
| | BE CUT NOR ROOF FRAMING TO BE STRENGTHEN FOR THE |
| | ADDITIONAL WEIGHT AND POINT LOADING OF THE ROOF JOIST. |
| | 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | RESPONSE: |
| | PLANS STILL DON'T SHOW ANY STRUCTURAL INFORMATION ABOUT |
| | THE ROOF TOP DECK PREPARATION TO RECEIVE THE NEW |
| | ADDITIONAL LOAD OF THE A/C CONDENSER UNIT. IT DOESN'T |
| | SPECIFY THE STRUCTURAL SUPPORTS. SEC. 107.2.1 CITY |
| | AMENDMENTS. |
| | |
| | ORIGINAL COMMENT: |
| | 7) 2017 FBC-B 1013.6 MECHANICAL EQUIPMENT. GUARDS SHALL |
| | BE PROVIDED WHERE APPLIANCES, EQUIPMENT, FANS, ROOF |
| | HATCH OPENINGS OR OTHER COMPONENTS THAT REQUIRE SERVICE |
| | ARE LOCATED WITHIN 10 FEET (3048 MM) OF A ROOF EDGE OR |
| | OPEN SIDE OF A WALKING SURFACE AND SUCH EDGE OR OPEN |
| | SIDE IS LOCATED MORE THAN 30 INCHES ABOVE THE FLOOR, |
| | ROOF OR GRADE BELOW. THE GUARD SHALL BE CONSTRUCTED SO |
| | AS TO PREVENT THE PASSAGE OF A SPHERE 21 INCHES IN |
| | DIAMETER. THE GUARD SHALL EXTEND NOT LESS THAN 30 |
| | INCHES BEYOND EACH END OF SUCH APPLIANCE, EQUIPMENT, |
| | FAN OR COMPONENT. |
| | |
| | RESPONSE: |
| | PROVIDE EXACT LOCATION OF ROOF TOP UNIT. COORDINATE |
| | WITH ITEM #6 ABOVE. |
| | |
| | 8) OK. |
| | |
| | |
| | 9) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | |
| | NEW COMMENT: |
| | 10-THIS BUILDING IS NOT SPRINKLERED. ACCORDING TO |
| | EXCEPTION #4 OF SEC. 1020.1 FBC THE CORRIDORS NEED TO |
| | BE FIRE RATED IN ACCORDANCE WITH TABLE 1020.1. REVISE |
| | PLANS AS REQUIRED TO COMPLY. |
| | |
| | |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | (561)805-6712 |
| | [email protected] |
| | |
| | |
| | |