| Date |
Text |
| 2019-01-02 17:18:38 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #18111103 |
| | 1/2/18 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) A HAZARDOUS EXHAUST SYSTEM MAY BE REQUIRED FOR THE |
| | MATERIALS TESTING LAB UNLESS THE EXCEPTION UNDER |
| | SECTION 510.2 FBC M IS MET. PLEASE REVIEW THE CODE |
| | SECTION AND EXCEPTION COPIED BELOW. EVIDENCE OF |
| | COMPLIANCE WILL REQUIRE A NARRATIVE THAT DESCRIBES THE |
| | PROCESSES THAT OCCUR IN THE LAB, A LIST OF MATERIALS TO |
| | BE TESTED, A LIST OF CHEMICALS USED IN THE TESTING |
| | PROCESS, AND THE QUANTITIES OF MATERIALS AND CHEMICALS |
| | TO BE USED AND STORED IN THE LAB. SEE ALSO SECTION |
| | 414.1.3 AND PROVIDE MSDS SHEETS FOR ALL MATERIALS AND |
| | CHEMICALS. |
| | |
| | 510.2 WHERE REQUIRED. |
| | A HAZARDOUS EXHAUST SYSTEM SHALL BE REQUIRED WHEREVER |
| | OPERATIONS INVOLVING THE HANDLING OR PROCESSING OF |
| | HAZARDOUS MATERIALS, IN THE ABSENCE OF SUCH EXHAUST |
| | SYSTEMS AND UNDER NORMAL OPERATING CONDITIONS, HAVE THE |
| | POTENTIAL TO CREATE ONE OF THE FOLLOWING CONDITIONS: |
| | |
| | 1.A FLAMMABLE VAPOR, GAS, FUME, MIST OR DUST IS PRESENT |
| | IN CONCENTRATIONS EXCEEDING 25 PERCENT OF THE LOWER |
| | FLAMMABILITY LIMIT OF THE SUBSTANCE FOR THE EXPECTED |
| | ROOM TEMPERATURE. |
| | |
| | 2.A VAPOR, GAS, FUME, MIST OR DUST WITH A HEALTH-HAZARD |
| | RATING OF 4 IS PRESENT IN ANY CONCENTRATION. |
| | |
| | 3.A VAPOR, GAS, FUME, MIST OR DUST WITH A HEALTH-HAZARD |
| | RATING OF 1, 2 OR 3 IS PRESENT IN CONCENTRATIONS |
| | EXCEEDING 1 PERCENT OF THE MEDIAN LETHAL CONCENTRATION |
| | OF THE SUBSTANCE FOR ACUTE INHALATION TOXICITY. |
| | |
| | EXCEPTION: LABORATORIES, AS DEFINED IN SECTION 510.1, |
| | EXCEPT WHERE THE CONCENTRATIONS LISTED IN ITEM 1 ARE |
| | EXCEEDED OR A VAPOR, GAS, FUME, MIST OR DUST WITH A |
| | HEALTH-HAZARD RATING OF 1, 2, 3 OR 4 IS PRESENT IN |
| | CONCENTRATIONS EXCEEDING 1 PERCENT OF THE MEDIAN LETHAL |
| | CONCENTRATION OF THE SUBSTANCE FOR ACUTE INHALATION |
| | TOXICITY. |
| | |
| | 2) : REFER TO SECTION 809.2 FBC EX AND PROVIDE MINIMUM |
| | VENTILATION CALCULATIONS FOR ALL ROOMS AND SPACES PER |
| | TABLE 403.3.1.1 FBC M. PROVIDE A SCHEDULE THAT |
| | INDICATES THE REQUIRED AND PROVIDED CFMS OF OUTDOOR |
| | AIR. CONCERNING THE HOTEL TOUCHDOWN, LAN AND WORK |
| | ROOMS, PLEASE CLARIFY WHAT FUNCTIONS TAKE PLACE IN THE |
| | ROOMS AND HOW THE VENTILATION IS BEING SIZED. |
| | |
| | 3) SHEET M-1: PROVIDE AN EQUIPMENT SCHEDULE FOR EF-2 IN |
| | THE LAB AND INDICATE HOW THE FAN WAS SIZED- PROVIDE AN |
| | EXHAUST VENTILATION CALCULATION AND A SEQUENCE OF |
| | OPERATION. PLEASE NOTE THAT EXHAUST AT A RATE OF 1.0 |
| | CFMS PER SF. IS REQUIRED FOR A LAB IN ACCORDANCE WITH |
| | TABLE 403.3.1.1 FBC M. |
| | |
| | 4) M-1: THE EXHAUST TERMINATION FOR THE HOOD IN THE LAB |
| | APPEARS TO BE WITHIN THE REQUIRED MINIMUM 10' CLEARANCE |
| | TO THE ENTRY DOOR AND THE OVERHEAD DOOR- SEE SECTION |
| | 501.3.1 FBC M AND SHOW COMPLIANCE. |
| | |
| | 5) M-1: LAB EXHAUST HOOD: A) CLARIFY THE PURPOSE AND |
| | FUNCTION OF THE HOOD. WHAT IS THE PROCESS THAT OCCURS |
| | UNDER THE HOOD AND WHAT FUMES, DUSTS, MISTS ETC. ARE |
| | BEING EXHAUSTED. B) PROVIDE AN EQUIPMENT SCHEDULE FOR |
| | THE HOOD AND SUBMIT MANUFACTURER'S SPECIFICATIONS. C) |
| | PROVIDE ENLARGED DIMENSIONED ELEVATION AND PLAN VIEWS |
| | OF THE HOOD THAT INDICATE REQUIRED INSTALLATION AND |
| | CLEARANCE HEIGHTS ETC. |
| | |
| | 6) M-1: INDICATE HOW O/A IS BEING PROVIDED AND |
| | CONTROLLED FOR AHU'S 1, 2, & 3. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |