| 2018-12-03 14:57:02 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | |
| | |
| | 1) SHEET A 1 - THERE IS AN INDICATION OF A LAB; |
| | HOWEVER, THERE IS NO INDICATION OF WHAT THIS LAB IS |
| | BEING USED FOR. |
| | |
| | PLEASE PROVIDE DETAIL INFORMATION OF THE TYPE OF WORK |
| | PERFORMED WITHIN THIS LAB.. |
| | |
| | |
| | |
| | |
| | 2) SHEET CS 1 - THERE ARE INDICATIONS OF SEPARATE |
| | OCCUPANCY LOADS; HOWEVER, THERE IS NO OCCUPANCY |
| | CLASSIFICATION PER THE FLORIDA FIRE PREVENTION CODE. |
| | |
| | PLEASE PROVIDE THE OCCUPANCY CLASSIFICATION AND WHETHER |
| | IT IS MIXED OR SEPARATED. (IT APPEARS TO BE SPEPARATED |
| | ON SHEET A 1, NEED FOR CLARIFICATION PURPOSES) |
| | |
| | |
| | |
| | |
| | 3) SHEET A 1 - THERE IS AN INDICATION OF OVEN WITHIN |
| | THE LAB ROOM. THERE IS NO INDICATION OF WHAT THIS OVEN |
| | IS USED FOR AND OR ANY VENTING REQUIREMENTS. |
| | |
| | PLEASE PROVIDE DETAILS. |
| | |
| | ANY PROPOSED VENTING SHALL BE PER NFPA 96 AND UNDER |
| | SEPARATE SHOP DRAWINGS. PROVIDE AN APPLICABLE NOTE. |
| | |
| | |
| | |
| | |
| | 4) SHEET A 1 - 1 HOUR FIRE WALLS ARE INDICATED AROUND |
| | THE LAB ROOM. PER # 2 ABOVE WHAT IS THE REQUIRED RATING |
| | OF THE SEPARATION OF OCCUPANCIES. IT MAY BE 2 HOURS. |
| | |
| | PLEASE REVIEW AND CORRECT OR JUSTIFY WITH APPLICABLE |
| | FIRE CODE REFERNECES. |
| | |
| | |
| | |
| | |
| | 5) SHEET A 1 - C2 RATED WALLS ARE INDICATED AROUND THE |
| | LAB, HOWEVER, AT THE BATHROOM AREA THE RATING STOPS AT |
| | THE DOOR EXPOSING THE INTERIOR OF THE BATHROOMS TO THE |
| | HAZARD. |
| | |
| | THE BATHROOM WALLS ARE REQUIRED TO BE HAVE THIS RATING. |
| | FOR DISSCUSSION PURPOSES, THE OUTSIDE BATHROOM WALLS |
| | INCLUDING THE DOORS WOULD NOT BE REQUIRED TO BE RATED. |
| | THE RATING WOULD STOP AT THE WALLS DIRECTLY IN CONTACT |
| | WITH THE LAB. |
| | |
| | PLEASE REVIEW AND CORRECT. |
| | |
| | |
| | |
| | 6) SHEET A 1 - THERE IS AN INDICATION OF B2 WALLS (BY |
| | DOOR 21) THAT APPEAR TO REQUIRE C2 RATINGS. |
| | |
| | PLEASE REVIEW AND CORRECT OR JUSTIFY WITH FIRE CODE |
| | REFERENCES. |
| | |
| | |
| | |
| | |
| | 7) SHEET A 1 - THERE ARE INDICATIONS OF B WALLS AROUND |
| | THE ELECTRIC ROOM. THERE IS NO CALL OUT FOR B WALLS. IN |
| | ADDITION, THERE WALLS APPEAR TO REQUIRE C2 RATINGS. |
| | |
| | PLEASE REIVEW AND CORRECT OR JUSTIFY WILL FIRE CODE |
| | REFERENCES. |
| | |
| | |
| | |
| | |
| | 8) SHEET A 2 - THE DOOR SCHEDULE HAS INDICATIONS OF C |
| | LABELS. |
| | |
| | FOR CLARIFICATION PURPOSES PLEASE PROVIDE FIRE RATING |
| | TIME FOR THESE DOORS PER THE FFPC AND ENSURE THE ARE IN |
| | COMPLIANCE WITH ANY CHANGES TO # 2 & 4. |
| | |
| | |
| | |
| | |
| | 9) SHEET E 2 - THERE ARE TWO (2) EXITS INDICATED FOR |
| | THE LAB AREA. BASED ON THE CLASSIFICATION OF THIS |
| | OCCUPANCY AND BEING SEPARATED FOR THE OTHER |
| | OCCUOPANCIES, THESE TWO (2) EXITS MAY BE REQUIRED PER |
| | THE FFPC TO BE SEPARATED BY 1/2 THE DIAGONAL OF THE |
| | SPACE SERVED. |
| | |
| | THESE EXITS APPEAR TO TOO CLOSE TO EACH OTHER TO MEET |
| | THIS REQUIREMENT. |
| | |
| | PER NFPA 101, CHAPTER 7, |
| | |
| | 7.5.1.3.2* WHERE TWO EXITS, EXIT ACCESSES, OR EXIT |
| | DISCHARGES ARE |
| | REQUIRED, THEY SHALL BE LOCATED AT A DISTANCE FROM ONE |
| | ANOTHER NOT |
| | LESS THAN ONE-HALF THE LENGTH OF THE MAXIMUM OVERALL |
| | DIAGONAL |
| | DIMENSION OF THE BUILDING OR AREA TO BE SERVED, |
| | MEASURED IN A |
| | STRAIGHT LINE BETWEEN THE NEAREST EDGE OF THE EXITS, |
| | EXIT ACCESSES, OR |
| | EXIT DISCHARGES, UNLESS OTHERWISE PROVIDED IN 7.5.1.3.3 |
| | THROUGH |
| | 7.5.1.3.5.. |
| | |
| | |
| | |
| | PLEASE REVIEW THE OCCUPANCY OF THE LAS PER THE FFPC AND |
| | THE REQUIRED EIXTING AND CORRECT IF APPLICABLE. |
| | |
| | |
| | |
| | 10) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | 11) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |