| 2018-12-18 17:53:15 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #18111084 |
| | 12/18/18 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET M-2.2 ADVISORY: AS NOTED ON THE PLAN, A |
| | SEPARATE PERMIT IS REQUIRED FOR THE KITCHEN EXHAUST |
| | HOOD, HOWEVER AN EYEBROW HOOD IS NOT PERMITTED FOR USE |
| | OVER HEAVY DUTY COOKING APPLIANCES- SECTIONS 507.5.2 |
| | AND 202 FBC M. |
| | |
| | 2) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE COOKING |
| | APPLIANCES- SECTION 623.1 FBC FG. |
| | |
| | 3) M-2.2: MAKEUP AIR FOR THE HOOD EXHAUST CANNOT BE |
| | USED AS COMBUSTION AIR FOR THE GAS-FIRED APPLIANCES- |
| | SEE SECTION 304.9.3 FBC FG. |
| | |
| | 4) M-2.2: A DUCT SMOKE DETECTOR IS REQUIRED IN THE |
| | SUPPLY AIR SYSTEM OF THE 5-TON AHU-1 PER SECTION |
| | 606.2.1 FBC M. PLEASE NOTE THAT AN EXEMPTION CAN BE |
| | APPLIED IF THE MANUFACTURER'S SPECIFICATIONS INDICATE |
| | THE AIR HANDLER IS NOT CAPABLE OF PRODUCING OVER 2000 |
| | CFMS OF SUPPLY AIR. |
| | |
| | 5) M.2-2: PROVIDE AUTOMATICALLY CONTROLLED SHUTOFF |
| | DAMPERS FOR THE O/A INTAKE DUCTS- SECTION C403.2.4.3 |
| | FBC EC. |
| | |
| | 6) M-2.2: PROVIDE ACCESS PANELS FOR THE ABOVE CEILING |
| | AIR HANDLERS- SECTION 306.1 FBC M. |
| | |
| | 7) M-2.2: PROVIDE CONDENSATE DISPOSAL PLANS FOR THE NEW |
| | AIR HANDLERS- SECTION 307.2.1 FBC M. |
| | |
| | 8) ENERGYGAUGE REPORT; THE COOLING SYSTEM CAPACITY |
| | LISTED ON THE FORM FOR SYSTEM 2 DOES NOT MATCH THE |
| | CAPACITY OF THE SYSTEM ON THE PLAN, AND MISSING FROM |
| | THE REPORT IS SYSTEM 3. |
| | |
| | 9) PLEASE NOTE THAT SEPARATE PERMITS ARE REQUIRED FOR |
| | THE KITCHEN EXHAUST HOOD, FIRE SUPPRESSION SYTEM, AND |
| | THE WALKIN COOLER AND FREEZER. |
| | |
| | 10) CLARIFY HOW THE MUA UNIT WAS SIZED FOR THE KITCHEN |
| | HOOD EXHAUST SYSTEM- PROVIDE A CALCULATION. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |