2018-12-12 13:01:18CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. ONE PERMIT APPLICAITON STATES $200,000 FOR VALUE,
 ANOTHER STATES $50,000. PROVIDE COPY OF SIGNED CONTRACT
 WITH SCOPE AND VALUE OF WORK, TO INCLUDE ALL MATERIALS
 AND LABOR. THIS IS FOR TOTAL PROJECT, NOT JUST
 ELECTRICAL. FBC 109.3
 2. RISER DIAGRAM SHOWS PANEL KP3 FED FROM PANEL KP2.
 THE PANEL SCHEDULES SHOW IT FED FROM KP1. PROVIDE
 CLARIFICATION AND/OR CORRECTIONS. WPB FBC 107.2.1
 3. ALL KITCHEN RECEPTACLES, INCLUDING DROP CORDS,
 REQUIRED GFCI PROTECTION. PROVIDE CORRECTION. NEC 210.8
 4. HOT WATER HEATERS IN PANELS A AND KP2 SHOULD BE
 CALCULATED AS A CONTINUOUS LOAD. PROVIDE CORRECTION.
 NEC 422.13
 5. BASED ON SITE VISIT BY INSPECTOR, THE EXISTING RISER
 DIAGRAM DOES NOT APPEAR TO BE CORRECT AS SHOWN. THIS
 RISER DIAGRAM EVEN DIFFERS FROM THE ONE PROVIDED FOR
 PERMIT 18050930. IF THERE IS ADDITIONAL WORK TO THE
 SERVICE PLANNED, PROVIDE AN ACCURATE EXISTING RISER
 DIAGRAM AS WELL AS A PROPOSED RISER DIAGRAM. THERE
 SHOULD BE MAIN DISCONNECTS PER NEC 230.70(A). NEC
 215.5, 230.70, 230.71, 230.72; WPB FBC 107.2.1
 6. PROVIDE LOCATION OF SERVICE AND PANELS ON PLAN. WPB
 FBC 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved