2019-02-27 08:58:16BUILDING REVIEW APPROVED WITH PROVISO:
 1-PROVIDE COMPLETE ENERGY CALCULATIONS FOR THE MAIN
 HOUSE. ONLY COVER PAGE WAS SUBMITTED.
 2-PROVIDE PRODUCT APPROVAL FOR: A)INSWING ARCHED ENTRY
 DOOR SIZE AS SHOWN ON PLANS. B) PROVIDE CURRENT
 POLYSTICK TU-PLUS PRODUCT APPROVAL. FL5259-R10
 SUBMITTED IS TOO OLD. AND CLEARLY IDENTIFY WHICH
 ASSEMBLY IS GOING TO BE USED.
 3- PROVIDE COMPLETE DETAILS/SPECIFICATIONS FOR THE
 FOOTING OF PRIVACY WALL WHEN THE WALL IS LOCATED AT THE
 PROPERTY LINE. FOOTING CAN NOT ENCROACH BEYOND THE
 PROPERTY LINE.
  