| 2019-01-03 11:37:52 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 5TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH |
| | EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| | FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | 1ST REVIEW: DENIED |
| | PLUMBING COMMENTS |
| | 1. KITCHEN: FLOOR PLAN SINK AT WINDOW HAS HORIZONTAL |
| | DRY VENT EXTENDING FROM THE FIXTURE DRAIN AND WOULD BE |
| | S-TRAPPED; SEE NOTES C AND D FOR VIOLATIONS. RISER |
| | DIAGRAM IS CORRECT AS LONG AS VET RISES 6" ABOVE THE |
| | FLOOD LEVEL RIM BEFORE OFFSETTING (A STUDOR VENT COULD |
| | ALSO BE USED). THE FLOOR PLAN AND THE RISER DIAGRAM |
| | NEED TO MATCH PER WPB FBC 107.2.1. |
| | 2. GUEST BATH: LAVATORY AND SHOWER ARE S-TRAPPED AND |
| | ALSO HAVE HORIZONTAL DRY VENTS EXTENDING FROM THE |
| | FIXTURE DRAIN; SEE NOTES A, C AND D FOR VIOLATIONS. |
| | 3. MASTER BATHROOM: SHOWER DRAIN HAS TO MUCH FALL; SEE |
| | NOTE B FOR VIOLATION. |
| | 4. BATH #2: SHOWER IS S-TRAPPED AND HAS A HORIZONTAL |
| | DRY VENT EXTENDING FROM THE FIXTURE DRAIN; SEE NOTES C |
| | AND D FOR VIOLATIONS. |
| | 5. LAUNDRY ROOM: SEE NOTES E AND F FOR VIOLATION. |
| | |
| | NOTES |
| | A. FBC RES P3105.2 FIXTURE DRAINS. |
| | THE TOTAL FALL IN A FIXTURE DRAIN RESULTING FROM PIPE |
| | SLOPE SHALL NOT EXCEED ONE PIPE DIAMETER, NOR SHALL THE |
| | VENT PIPE CONNECTION TO A FIXTURE DRAIN, EXCEPT FOR |
| | WATER CLOSETS, BE BELOW THE WEIR OF THE TRAP. |
| | |
| | B. FBC RES P3105.2 FIXTURE DRAINS. |
| | THE TOTAL FALL IN A FIXTURE DRAIN RESULTING FROM PIPE |
| | SLOPE SHALL NOT EXCEED ONE PIPE DIAMETER, NOR SHALL THE |
| | VENT PIPE CONNECTION TO A FIXTURE DRAIN, EXCEPT FOR |
| | WATER CLOSETS, BE BELOW THE WEIR OF THE TRAP. SHOWER |
| | DRAIN ROLLS UP TO CROSS OVER 3? BRANCH IS PROHIBITED |
| | UNLESS REVENTED AT THE HIGHER ELEVATION. |
| | |
| | C. FBC RES P3104.3 P3104.4 VENT CONNECTION TO DRAINAGE |
| | SYSTEM. |
| | A DRY VENT CONNECTING TO A HORIZONTAL DRAIN SHALL |
| | CONNECT ABOVE THE CENTERLINE OF THE HORIZONTAL DRAIN |
| | PIPE. |
| | P3104.4 VENTS SHALL RISE VERTICALLY TO A POINT 6? ABOVE |
| | THE FLOOD LEVEL RIM OF THE HIGHEST FIXTURE BEING SERVED |
| | |
| | D. FBC RES P3201.5 PROHIBITED TRAP DESIGNS. |
| | S-TRAPS ARE PROHIBITED; SEE ALL |
| | |
| | E. FBC RES P2601.1, FBC PL 406.2 THE FIXTURE DRAIN FOR |
| | THE STANDPIPE SERVING AN AUTOMATIC CLOTHES WASHER SHALL |
| | CONNECT TO A 3? OR LARGER FIXTURE BRANCH OR STACK. |
| | |
| | F. WPB FBC 107.2.1 LAUNDRY SINK SHOWN ON SECOND FLOOR |
| | PLAN VIEW SHALL BE SHOWN ON THE SANITARY RISER DIAGRAM |
| | |
| | DIGITAL PLANS HAVE BEEN REDLINED AND MAY BE REVIEWED |
| | FOR ADDITIONAL CLARIFICATION |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | EMAIL [email protected] |
| | PHONE 561-805-6715 |