Plan Review Notes
Plan Review Notes For Permit 18111079
Permit Number 18111079
Review Stop P
Sequence Number 1
Notes
Date Text
2019-01-03 11:37:52CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 5TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 1ST REVIEW: DENIED
 PLUMBING COMMENTS
 1. KITCHEN: FLOOR PLAN SINK AT WINDOW HAS HORIZONTAL
 DRY VENT EXTENDING FROM THE FIXTURE DRAIN AND WOULD BE
 S-TRAPPED; SEE NOTES C AND D FOR VIOLATIONS. RISER
 DIAGRAM IS CORRECT AS LONG AS VET RISES 6" ABOVE THE
 FLOOD LEVEL RIM BEFORE OFFSETTING (A STUDOR VENT COULD
 ALSO BE USED). THE FLOOR PLAN AND THE RISER DIAGRAM
 NEED TO MATCH PER WPB FBC 107.2.1.
 2. GUEST BATH: LAVATORY AND SHOWER ARE S-TRAPPED AND
 ALSO HAVE HORIZONTAL DRY VENTS EXTENDING FROM THE
 FIXTURE DRAIN; SEE NOTES A, C AND D FOR VIOLATIONS.
 3. MASTER BATHROOM: SHOWER DRAIN HAS TO MUCH FALL; SEE
 NOTE B FOR VIOLATION.
 4. BATH #2: SHOWER IS S-TRAPPED AND HAS A HORIZONTAL
 DRY VENT EXTENDING FROM THE FIXTURE DRAIN; SEE NOTES C
 AND D FOR VIOLATIONS.
 5. LAUNDRY ROOM: SEE NOTES E AND F FOR VIOLATION.
  
 NOTES
 A. FBC RES P3105.2 FIXTURE DRAINS.
 THE TOTAL FALL IN A FIXTURE DRAIN RESULTING FROM PIPE
 SLOPE SHALL NOT EXCEED ONE PIPE DIAMETER, NOR SHALL THE
 VENT PIPE CONNECTION TO A FIXTURE DRAIN, EXCEPT FOR
 WATER CLOSETS, BE BELOW THE WEIR OF THE TRAP.
  
 B. FBC RES P3105.2 FIXTURE DRAINS.
 THE TOTAL FALL IN A FIXTURE DRAIN RESULTING FROM PIPE
 SLOPE SHALL NOT EXCEED ONE PIPE DIAMETER, NOR SHALL THE
 VENT PIPE CONNECTION TO A FIXTURE DRAIN, EXCEPT FOR
 WATER CLOSETS, BE BELOW THE WEIR OF THE TRAP. SHOWER
 DRAIN ROLLS UP TO CROSS OVER 3? BRANCH IS PROHIBITED
 UNLESS REVENTED AT THE HIGHER ELEVATION.
  
 C. FBC RES P3104.3 P3104.4 VENT CONNECTION TO DRAINAGE
 SYSTEM.
 A DRY VENT CONNECTING TO A HORIZONTAL DRAIN SHALL
 CONNECT ABOVE THE CENTERLINE OF THE HORIZONTAL DRAIN
 PIPE.
 P3104.4 VENTS SHALL RISE VERTICALLY TO A POINT 6? ABOVE
 THE FLOOD LEVEL RIM OF THE HIGHEST FIXTURE BEING SERVED
  
 D. FBC RES P3201.5 PROHIBITED TRAP DESIGNS.
 S-TRAPS ARE PROHIBITED; SEE ALL
  
 E. FBC RES P2601.1, FBC PL 406.2 THE FIXTURE DRAIN FOR
 THE STANDPIPE SERVING AN AUTOMATIC CLOTHES WASHER SHALL
 CONNECT TO A 3? OR LARGER FIXTURE BRANCH OR STACK.
  
 F. WPB FBC 107.2.1 LAUNDRY SINK SHOWN ON SECOND FLOOR
 PLAN VIEW SHALL BE SHOWN ON THE SANITARY RISER DIAGRAM
  
 DIGITAL PLANS HAVE BEEN REDLINED AND MAY BE REVIEWED
 FOR ADDITIONAL CLARIFICATION
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
  