| Date |
Text |
| 2019-01-03 13:01:53 | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH |
| | EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| | FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | 1ST REVIEW: DENIED |
| | GAS COMMENTS |
| | GAS PLAN NOT SUPPLIED. IS GAS SERVICE AVAILABLE THAT |
| | WILL SUPPORT THE REQUIREMENTS OF THE RESIDENCE? A |
| | SEPERATE PERMIT WILL BE REQUIRED FOR THE GAS. |
| | |
| | 1. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE |
| | LENGTH OF ALL CUT SECTIONS OF PIPE PER FBC RES |
| | G2413.4.1, G2413.4.2. |
| | 2. SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL |
| | PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE |
| | CORRUGATED STAINLESS STEEL TUBING (IF APPLICABLE) FOR |
| | EACH PIPE SIZE. WPB FBC 107.2.1. |
| | 3. TYPE OF GAS (LP OR NATURAL). WPB FBC 107.2.1. IF |
| | NATURAL, SHOW METER LOCATION ON THE PLAN. IF LP PROVIDE |
| | THE FOLLOWING: |
| | A. CLEARLY SHOW THE LOCATION AND CAPACITY OF LP |
| | TANK(S), TYPE OF TANK (DOT OR ASME), THE DISTANCE OF |
| | THE TANK FROM THE EXTERIOR BUILDING WALL AND ADJACENT |
| | PROPERTY LINES, THE DISTANCE OF THE TANK FROM ALL |
| | SOURCES OF IGNITION, OTHER CONTAINERS, BUILDINGS, AND |
| | THE LOCATION OF ANY BUILDING OPENINGS BELOW THE RELIEF |
| | VALVE OF THE TANK PER NFPA 58, TABLE 3-2.2.2. |
| | B. CLEARLY INDICATE ON THE PLAN IF THE LP TANK IS ABOVE |
| | GROUND OR BELOW GROUND, AND SHOW THE METHOD OF REQUIRED |
| | PROTECTION FOR THE LP TANK AND APPURTENANCES PER NFPA |
| | 58. IF THE TANK IS BELOW GROUND IT SHALL BE ANCHORED |
| | PER NFPA 58 SEC.3-2.2.7 (H). IF ABOVE GROUND, THE TANK |
| | SHALL BE SECURELY ANCHORED TO WITHSTAND 170 MPH ULT |
| | WIND LOAD PER THE FLORIDA BUILDING CODE. |
| | 4.LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL BTU |
| | LOAD ON THE SYSTEM. REFER TO THE FBC RES SEC. G2413.3, |
| | G2413.4 AND TABLES G2413.4 (1) THROUGH G2413.4(21). |
| | 5. SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS |
| | METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND / OR SYSTEM PER THE FBC RES |
| | SEC. G 2413.4.1, G2413.4.2. |
| | 6. INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM |
| | ON THE PLAN PER FBC RES SEC. G2413.2, G2413.4.3. |
| | 7. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS / |
| | INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY |
| | COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND FBC RES |
| | SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED AND |
| | LABELED. THE INSTALLATION MANUALS FOR ALL GAS |
| | APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF |
| | INSPECTION. FBC RES SEC.G2408.1. |
| | 8. SHOW THE LOCATION OF THE TANKLESS WATER HEATER AND |
| | THE LOCATION AND DISTANCE OF ANY OPERABLE DOORS OR |
| | WINDOWS IN RELATION TO THE WATER HEATER. THE LOCATION |
| | OF THE WATER HEATER SHALL COMPLY WITH THE |
| | MANUFACTURER'S INSTALLATION INSTRUCTIONS. WPB FBC |
| | 107.2.1 |
| | 9. PROVIDE APPLICABLE SIZING TABLES USED TO SIZE THE |
| | GAS SYSTEM OR PLACE A NOTE ON THE PLANS/DRAWINGS |
| | SPECIFYING WHICH SIZING TABLE(S) FROM THE GAS CODE OR |
| | OTHER STANDARD THAT WERE USED IN THE DESIGN OF THIS GAS |
| | SYSTEM. REFER TO THE FBC RES SEC. G2413.3, G2412.8, |
| | G2413.1, G2413.2, & G2413.3. |
| | 10. SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE |
| | PRESSURE REGULATORS WHEN APPLICABLE. REGULATORS |
| | INSTALLED ON THE EXTERIOR OF THE BUILDING SHALL BE |
| | APPROVED FOR OUTDOOR INSTALLATION. FBC RES SEC. |
| | G2421.1. |
| | 11. I HAVE NOTED THREE (3) TANKLESS WATER HEATERS ON |
| | PLAN SHEET P.01; PLAN SHEET E.03 INDICATES A GAS RANGE, |
| | A BBQ GRILL (GAS?). ADDITIONALLY A FUTURE GENERATOR IS |
| | SHOWN ON PLAN SHEET A.02 AS WELL AS E.01 AND E.03. |
| | INDICATE ALL GAS FIRED APPLIANCES AND EQUIPMENT, PIPING |
| | DIAGRAMS, CALCULATIONS, ETC. IN AN ORDERLY WAY ON THE |
| | PLANS. WPB FBC 107.2.1. |
| | 12. SHOW THE LOCATION OF ALL MP (STEP-DOWN) REGULATORS. |
| | A LISTED SHUTOFF VALVE SHALL BE INSTALLED IMMEDIATELY |
| | AHEAD OF EACH MP REGULATOR. FBC RES SEC. G 2420.4 |
| | 13. SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE |
| | PRESSURE REGULATORS. REGULATORS INSTALLED ON THE |
| | EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR |
| | INSTALLATION. 2014 FGC SEC.410.1, 2017 FBC-RES. SEC. |
| | G2421.1. |
| | 14. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE FBC |
| | RES SEC. G 2407.1 AND G2439.4 |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | EMAIL [email protected] |
| | PHONE 561-805-6715 |
| | |