2018-12-19 16:20:07FAILED
  
 PLEASE PROVIDE WRITTEN RESPONSES TO COMMENTS.
  
 1) PLEASE PROVIDE VERIFICATION IN THE FORM OF A SURVEY
 TO VERIFY THAT THE PROPOSED FACILITIES ARE LOCATED
 WITHIN THE RIGHT-OF-WAY AND NOT ON PRIVATE PROPERTY.
 THE SUPPLIED PLAN IS SIGNED AND SEALED BY AN ENGINEER,
 NOT A SURVEYOR. THE BACK OF A SIDEWALK IS TYPICALLY THE
 BOUNDARY BETWEEN THE RIGHT-OF-WAY AND THE PRIVATE
 PROPERTY, BUT THE PLAN SHOWS THE SIDEWALKS LOCATED AWAY
 FROM THE PROPERTY LINE.
  
 2) PROVIDE CONSENT FROM FPL, THE OWNER OF THE UTILITY
 POLE, THAT PERMITS THE PLACEMENT OF THE ANTENNAS AND
 RELATED EQUIPMENT ON IT.
  
 3) THE CITY REQUIRES THAT THE EQUIPMENT CABINETS
 (UTILITY METER, DISCONNECT AD NEMA BOX) BE SCREENED BY
 LANDSCAPE. PLEASE SHOW HOW THIS WILL OCCUR. NOTE: WHILE
 THE PLANS CALL THE EQUIPMENT CABINETS' HEIGHT AT A
 MAXIMUM OF SIX (6) FEET, PLEASE CONSIDER HAVING THEM
 MOUNTED ON A SHORTER POLE TO MINIMIZE THE VISUAL IMPACT
 (A LOWER LANDSCAPE SCREEN COULD THEN BE USED).
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
 [email protected]
2018-11-30 08:19:27ROUTED TO AJV