Plan Review Notes
Plan Review Notes For Permit 18111050
Permit Number 18111050
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2018-12-06 11:23:00PERMIT # 18111050
 REVIEW COMMENTS - FIRE DEPARTMENT
  
  
 1. THE OCCUPANT LOAD FOR THESE TENTS SHALL COMPLY WITH
 THE OCCUPANT LOAD FACTOR AS LISTED UNDER NFPA 101:
 CHAPTER 7, TABLE 7.3.1.2.
  
 2. PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
 PROVIDE TYPE K EXTINGUISHERS WHEN COOKING WITH GREASE
 OR WHEN PRODUCING SMOKE OR GREASE-LADEN VAPORS.
  
 3. EMERGENCY LIGHTING AND ILLUMINATED EXIT SIGNS ARE
 REQUIRED FOR TENTS EXCEEDING 1,200 SQUARE FEET.
  
 4. POST WEATHERPROOF NO SMOKING SIGNS IN CONSPICUOUS
 LOCATIONS.
  
 5. GENERATORS AND OTHER INTERNAL COMBUSTION POWER
 SOURCES SHALL BE SEPARATED FROM TENTS BY A MINIMUM OF 5
 FEET AND SHALL BE PROTECTED FROM CONTACT BY FENCING OR
 ENCLOSURE.
  
  
  
 THANK YOU,
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
  