| Plan Review Notes For Permit 18111043 |
| Permit Number |
18111043 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-12-03 10:51:25 | SENT TO ENGINEERING DUE TO UNDERGROUND VAULT AND NEW | | | BACKFLOW. | | | | | | PML | | 2018-12-03 10:50:12 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | | | | 1) SHEET FP O - THERE IS AN INDICATION UNDER PROJECT # | | | AS VALUE STORE IN HOLLYWOOD FL. | | | | | | PLEASE REVIEW AND CORRECT. | | | | | | | | | | | | 2) THERE ARE NO MANUFACTURESE SPECIFICATION SHEETS FOR | | | THE PROPOSED BACKFLOW. | | | | | | PLEASE PROVIDE THE APPLICABLE SPEC SHEETS TO ENSURE | | | THEY MEET THE CITY ENGINEERING SPECIFICATIONS. | | | | | | | | | | | | 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | | | | 4)ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | | | | |
|