Plan Review Notes
Plan Review Notes For Permit 18111038
Permit Number 18111038
Review Stop P
Sequence Number 2
Notes
Date Text
2019-08-27 13:54:51PLUMBING COMMEMTS: APPROVED W/PROVISO
 1. ALL WORK PER CITY CODES SUBJECT TO FIELD INSPECTOR'S
 APPROVAL
 2.PER FBC PL 912.1, ONLY BATHROOM GROUP FIXTURES MAY
 CONNECT TO THE WET VENT. CONNECT EWC DOWNSTREAM OF THE
 WET VENT AS RED LINED ON PLAN SHEET 3.0P.
 3. PER FBC PL 416.5, PROVIDE TEMPERED WATER TO EACH
 LAVATORY THROUGH AN APPROVED TEMPERATURE LIMITING
 DEVICE CONFORMING TO ASSE 1070 OR CSA B125.3 AS RED
 LINED ON PLAN SHEET 3.0P.
  