| 2018-12-18 12:38:34 | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 18111038 |
| | ADD: 124 N DIXIE HWY. |
| | CONT: GARBER CONSTRUCTION |
| | TEL: 561-929-2505 |
| | E-MAIL: |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: TUES. DEC. 18/2018 |
| | ACTION: DENIED |
| | |
| | 1) THE ARCHITECTURAL SHEET 1.0A NOTE 9 INDICATES THE |
| | REMOVAL OF THE FRONT ENTRY DOOR AND SIDE ENTRY DOOR. |
| | THE PLANS INDICATE TO CREATE A NEW RECESSED DOUBLE |
| | GLASS DOOR SYSTEM IN THE FRONT OF THE BUILDING. THE |
| | PRODUCT APPROVAL SUBMITTED A MIAMI-DADE NOA SERIES |
| | ?SE-3550? OUTSWING DOOR WAS SUBMITTED. PLEASE NOTE |
| | COMPLIANCE WITH W. P. B. 107.3.4. PRODUCT APPROVALS. |
| | THOSE PRODUCTS WHICH ARE REGULATED BY FLORIDA |
| | ADMINISTRATIVE CODE RULE 61G20 SHALL BE REVIEWED AND |
| | APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO |
| | SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 2) PLEASE NOTE THE MIAMI-DADE NOA SERIES ?SE-3550? NOA |
| | # 17-1114.01 HAS 15 PAGES OF TECHNICAL PAGES. PAGE 11 |
| | OF 15 HAS LOCKING DETAILS 3, 4, & 5 WHEREAS PAGE 6 OF |
| | 15 HAS LOCKING OPTIONS 1, 2 & 6. THE OPTIONS ON PAGE 6 |
| | ARE ALL PANIC HARDWARE. PLEASE NOTE NEITHER THE |
| | CONTRACTOR NOR THE DESIGNER OF RECORD HAVE CIRCLED |
| | WHICH LOCKING OPTION AND ASSOCIATE PRESSURE ARE TO BE |
| | INSTALLED. |
| | PLEASE PROVIDE COMPLIANCE WITH THE 2017 FBC-B 1010.1.10 |
| | PANIC AND FIRE EXIT HARDWARE. DOORS SERVING A OCCUPANT |
| | LOAD OF 50 OR MORE IN A GROUP A SHALL NOT BE PROVIDED |
| | WITH A LATCH OR LOCK OTHER THAN PANIC HARDWARE OR FIRE |
| | EXIT HARDWARE. |
| | |
| | 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | |