Plan Review Notes
Plan Review Notes For Permit 18111036
Permit Number 18111036
Review Stop B
Sequence Number 1
Notes
Date Text
2018-11-29 09:39:49****CORRECTIONS****
 W.P.B. PERMIT: 18111036
 REVIEWED: NOVEMBER 29, 2018
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER I
 [email protected]
 561-805-6718
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC AMENDED = FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC ENERGY = FBC ENERGY CONSERVATION
  
 1. [FBC 1503.5]ROOF VENTILATION. ATTIC VENTILATION
 SHALL BE PROVIDED
 IN ACCORDANCE WITH SECTION 1203.2
 SUPPLY VENTING CALCULATIONS FOR THE ATTIC AND HOW THE
 AREA OF VENTING WILL BE ACHIEVED, OR FOLLOW R805.5 FOR
 UNVENTED.
 A. WHAT IS THE AREA OF VENTING REQ?D?
 B. HOW MUCH IS EACH SOLAR FAN PROVIDE?
 C. SHOW LOCATIONS OF SOLOR FANS ON SKETCH.
 D. PROVIDE SPEC SHEET THAT SHOWS THESE SOLAR VENTS CAN
 BE INSTALLED ON FLAT ROOF.
 E. MARK ON PRODUCT APPROVAL WHAT PRODUCT IS BEING
 INSTALLED.
  
 2. [FBC 1503.4]ROOF DRAINAGE
 PROVIDE ROOF DRAIN CALCULATIONS AND DESIGN TO COMPLY
 WITH SECTIONS 1106 AND 1107, AS APPLICABLE, OF THE
 FLORIDA BUILDING CODE, PLUMBING, CHAPTER 11.
 [FBC 1503.4]PROVIDE EXISTING SCUPPERS SIZING TO MEET
 DRAINAGE REQUIREMENTS IN FBC PLUMBING CHAPTER 11.
 ARE THERE ROOF DRAINS?
 IF SCUPPERS ONLY THEN SEE COMMENT BELOW.
 [FBC 1503.4.2.1]OVERFLOW SCUPPERS. WHEN OTHER MEANS OF
 DRAINAGE OF OVERFLOW WATER IS NOT PROVIDED, OVERFLOW
 SCUPPERS SHALL BE PLACED IN WALLS OR PARAPETS NOT LESS
 THAN 2 INCHES (51 MM) NOR MORE THAN 4 INCHES (102
 MM) ABOVE THE FINISHED ROOF COVERING AND SHALL BE
 LOCATED AS CLOSE AS PRACTICAL TO REQUIRED VERTICAL
 LEADERS
 OR DOWNSPOUTS OR WALL AND PARAPET SCUPPERS. AN OVERFLOW
 SCUPPER SHALL BE SIZED IN ACCORDANCE WITH THE FLORIDA
 BUILDING CODE, PLUMBING.
  
 NOTE:
 -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF MATERIALS REQUESTED.
 -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  