| 2018-11-29 09:39:49 | ****CORRECTIONS**** |
| | W.P.B. PERMIT: 18111036 |
| | REVIEWED: NOVEMBER 29, 2018 |
| | |
| | DYLAN BATTLES |
| | BUILDING PLANS EXAMINER I |
| | [email protected] |
| | 561-805-6718 |
| | |
| | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| | FBC AMENDED = FLORIDA BUILDING CODE,6TH EDITION (2017) |
| | FBC B = FBC BUILDING |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC ENERGY = FBC ENERGY CONSERVATION |
| | |
| | 1. [FBC 1503.5]ROOF VENTILATION. ATTIC VENTILATION |
| | SHALL BE PROVIDED |
| | IN ACCORDANCE WITH SECTION 1203.2 |
| | SUPPLY VENTING CALCULATIONS FOR THE ATTIC AND HOW THE |
| | AREA OF VENTING WILL BE ACHIEVED, OR FOLLOW R805.5 FOR |
| | UNVENTED. |
| | A. WHAT IS THE AREA OF VENTING REQ?D? |
| | B. HOW MUCH IS EACH SOLAR FAN PROVIDE? |
| | C. SHOW LOCATIONS OF SOLOR FANS ON SKETCH. |
| | D. PROVIDE SPEC SHEET THAT SHOWS THESE SOLAR VENTS CAN |
| | BE INSTALLED ON FLAT ROOF. |
| | E. MARK ON PRODUCT APPROVAL WHAT PRODUCT IS BEING |
| | INSTALLED. |
| | |
| | 2. [FBC 1503.4]ROOF DRAINAGE |
| | PROVIDE ROOF DRAIN CALCULATIONS AND DESIGN TO COMPLY |
| | WITH SECTIONS 1106 AND 1107, AS APPLICABLE, OF THE |
| | FLORIDA BUILDING CODE, PLUMBING, CHAPTER 11. |
| | [FBC 1503.4]PROVIDE EXISTING SCUPPERS SIZING TO MEET |
| | DRAINAGE REQUIREMENTS IN FBC PLUMBING CHAPTER 11. |
| | ARE THERE ROOF DRAINS? |
| | IF SCUPPERS ONLY THEN SEE COMMENT BELOW. |
| | [FBC 1503.4.2.1]OVERFLOW SCUPPERS. WHEN OTHER MEANS OF |
| | DRAINAGE OF OVERFLOW WATER IS NOT PROVIDED, OVERFLOW |
| | SCUPPERS SHALL BE PLACED IN WALLS OR PARAPETS NOT LESS |
| | THAN 2 INCHES (51 MM) NOR MORE THAN 4 INCHES (102 |
| | MM) ABOVE THE FINISHED ROOF COVERING AND SHALL BE |
| | LOCATED AS CLOSE AS PRACTICAL TO REQUIRED VERTICAL |
| | LEADERS |
| | OR DOWNSPOUTS OR WALL AND PARAPET SCUPPERS. AN OVERFLOW |
| | SCUPPER SHALL BE SIZED IN ACCORDANCE WITH THE FLORIDA |
| | BUILDING CODE, PLUMBING. |
| | |
| | NOTE: |
| | -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW |
| | OF MATERIALS REQUESTED. |
| | -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS |
| | OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS) |
| | SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT |
| | DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER |
| | SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID" |
| | OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS |
| | APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE |
| | NEED "VOID", RENDERING THEM NOT USABLE. |
| | |