| 2019-01-31 16:44:40 | 2ND REVIEW FBC-2017 MECHANICAL |
| | PERMIT #18111031 |
| | 1/31/19 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) IN RESPONSE TO THE 1ST REVIEW COMMENTS, THE |
| | ARCHITECT HAS SUBMITTED AN OLD PLAN FOR THE EXISTING |
| | FACILTIY THAT IS DATED AUGUST 2000. THERE ARE NO CITY |
| | STAMPS ON THE PLAN, NO ADDRESS SHOWN, AND NO COPY OF |
| | THIS PLAN IN OUR CITY RECORDS TO VALIDATE IT. THE |
| | CORRECTED NEW PLAN FOR THE FACILITY IS NOW SHOWING |
| | THREE NEW FANS INSTEAD OF ONE. PLEASE REVISE THE NEW |
| | PLAN TO ADDRESS COMMENTS #2- 5 BELOW. |
| | |
| | 2) SHEET ME-1: PROVIDE SIZING CALCULATION FOR THE NEW |
| | EXHAUST FANS BASED ON TABLE 403.3.1.1 FBC M. |
| | |
| | 3) ME-1: INDICATE THE SEQUENCE OF OPERATION FOR THE |
| | FANS. WILL THE FAN RUN CONTINUOUSLY OR INTERMITTENTLY? |
| | |
| | 4) ME-1: INDICATE HOW MAKEUP AIR IS TO BE PROVIDED FOR |
| | THE EXHAUST. |
| | |
| | 5) ME-1: SUBMIT A FL. PRODUCT APPROVAL OR MIAMI-DADE |
| | NOA FOR THE NEW LOUVERS- RULE 9N-3 FAC. |
| | |
| | |