| 2018-12-05 11:21:13 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6724 |
| | |
| | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| | FBC B = FBC BUILDING |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | FBC R = FBC RESIDENTIAL |
| | |
| | 1. FLORIDA STATE OR LOCAL PRODUCT APPROVALS REQUIRED |
| | FOR COMPONENTS AND CLADDING. THIS CAN BE A PROVISO ITEM |
| | FOR LARGE PROJECTS, BUT IT APPEARS THAT ROOFING AND THE |
| | LOUVER ARE A SIGNIFICANT PART OF THIS PROJECT. PROVIDE |
| | AT THIS TIME, REVIEWED BY DESIGNER OF RECORD, OR |
| | PROVIDE RATIONALE FOR REQUESTING A PROVISO, FBC B 1609. |
| | |
| | 2. S1, LOUVER OPENING DETAIL, THE DETAIL DOES NOT |
| | GRAPHICALLY SHOW REBAR ON SIDES OR BELOW THE PROPOSED |
| | NEW OPENING. EMBEDMENT INTO EXISTING IS NOT SPECIFIED. |
| | NOTE STATES TO VERIFY FILLED CELLS IN FIELD; IT APPEARS |
| | THAT AT LEAST ONE SIDE WILL BE REQUIRED TO BE |
| | CONSTRUCTED AS WELL AS THE SILL, UNLESS ENGINEER HAS |
| | KNOWLEDGE OF EXISTING CONDITIONS, PLEASE PROVIDE |
| | COMPLETE DETAILS OR CLARIFY. |
| | |
| | 2. THIS PERMIT WILL BE ISSUED WITH PROVISOS: |
| | |
| | A SEPARATE ROOF PERMIT IS REQUIRED. ROOFING CONTRACTOR |
| | IS TO INDICATE OPTIONS PROPOSED TO SHOW COMPLIANCE WITH |
| | DESIGN PRESSURES SPECIFIED ON SHEET S1. OR, THIS |
| | INFORMATION CAN BE PROVIDED AT THIS TIME. |
| | |
| | TRUSS ENGINEERING REVIEWED BY ENGINEER OF RECORD IS TO |
| | BE PROVIDED ON THE JOB PRIOR TO INSPECTION. |
| | |
| | |