2018-12-04 13:47:21****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 FBC R 301:
  
 1. PLEASE PROVIDE TYPE OF GLASS TO BE USE ON THE
 SLIDING DOORS AND WINDOWS TO DETERMINE THE MAXIMUM
 DESIGN PRESSURES FOR THESE PRODUCTS.
  
 2. PLEASE REVISED THE WALL PRESSURES (EXPOSURE D) AND
 SHUTTER MOUNTING CONNECTION PER PRODUCT APPROVAL (E.I.
 C1, C2, C3, C4 OR C5) ON THE "SCHEDULE FOR INSTALLATION
 OF OPENING PROTECTIVE DEVICES OR ASSEMBLIES" FORM.
  
 THE PRESSURES SPECIFIED (110/-200) EXCEED THE
 LIMITATIONS FOR THE PRODUCT SELECTED. NOTE THAT DESIGN
 PRESSURES APPEAR VERY HIGH. PER FBC R TABLES 301.2(2)
 AND (3), WORST CASE DESIGN PRESSURES EQUAL
 +48.36/-63.55 (170MPH, EXPOSURE D, 20MRH, ZONE 5).
  
 3. FLORIDA STATUTE 489.103, THE OWNER MUST SIGN THE
 OWNER/BUILDING AFFIDAVIT. THE OWNER IS REQUIRED TO
 PERSONALLY APPEAR AT THE BUILDING DIVISION.
  
  
  
  